Operating Guide | VLT® HVAC Drive FC 102
Maximum terminal load (DC-13)
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
Maximum terminal load (DC-1)
Maximum terminal load (DC-13)
Minimum terminal load on 1–3 (NC), 1–2 (NO)
Environment according to EN 60664-1
Relay 02 terminal number
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
Maximum terminal load (DC-1)
Maximum terminal load (DC-13)
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
Maximum terminal load (DC-1)
Maximum terminal load (DC-13)
Minimum terminal load on 4–6 (NC), 4–5 (NO)
Environment according to EN 60664-1
1
IEC 60947 parts 4 and 5.
2
Overvoltage Category II
3
UL applications 300 V AC 2 A.
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).

9.6.10 Control Card, +10 V DC Output

Terminal number
Output voltage
Maximum load
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.

9.6.11 Control Characteristics

Resolution of output frequency at 0–1000 Hz
System response time (terminals 18, 19, 27, 29, 32, 33)
Speed control range (open loop)
Speed accuracy (open loop)
All control characteristics are based on a 4-pole asynchronous motor.
Danfoss A/S © 2020.01
(1)
on 1–2 (NO) (Inductive load)
(1)
on 1–3 (NC) (Resistive load)
(1)
1–3 (NC) (Inductive load @ cosφ 0.4)
(1)
on 1–3 (NC) (Resistive load)
(1)
on 1–3 (NC) (Inductive load)
(1)
on 4–5 (NO) (Resistive load)
(1)
4–5 (NO) (Inductive load @ cosφ 0.4)
(1)
on 4–5 (NO) (Resistive load)
(1)
on 4–5 (NO) (Inductive load)
(1)
on 4–6 (NC) (Resistive load)
(1)
4–6 (NC) (Inductive load @ cosφ 0.4)
(1)
on 4–6 (NC) (Resistive load)
(1)
on 4–6 (NC) (Inductive load)
(2) (3)
Specifications
24 V DC 10 mA, 24 V AC 2 mA
Overvoltage category III/pollution degree 2
4–6 (break), 4–5 (make)
24 V DC 10 mA, 24 V AC 2 mA
Overvoltage category III/pollution degree 2
1:100 of synchronous speed
30–4000 RPM: Error ±8 RPM
AQ275556502253en-000101 / 130R0706| 137
24 V DC, 0.1 A
240 V AC, 2 A
240 V AC, 0.2 A
50 V DC, 2 A
24 V DC, 0.1 A
400 V AC, 2 A
240 V AC, 0.2 A
80 V DC, 2 A
24 V DC, 0.1 A
240 V AC, 2 A
240 V AC, 0.2 A
50 V DC, 2 A
24 V DC, 0.1 A
50
10.5 V ±0.5 V
25 mA
±0.003 Hz
≤2 ms