Parameter Descriptions
NOTE
When Auto Reset/ Warning is selected the frequency
converter opens up for automatic restart.
Overview of functions, alarms and warnings
3
3
Function
No Function
Safe Stop Alarm [1]*
Safe Stop
Warning
PTC 1 Alarm
PTC 1 Warning
PTC 1 & Relay A [6]
PTC 1 & Relay W [7]
PTC 1 & Relay A/
W
PTC 1 & Relay
W/A
W means warning and A means alarm. For further information,
see Alarms and Warnings in section Troubleshooting in the
Design Guide or the Operating Instructions
A dangerous failure related to Safe Stop will give Alarm:
Dangerous Failure [A72].
Please refer to the section Description of Alarm Word, Warning
Word and extended Status Word in the chapter Troubleshoot-
ing.
5-20 Terminal X46/1 Digital Input
Option:
[0]
No operation This parameter is active when option module
*
5-21 Terminal X46/3 Digital Input
Option:
[0]
No operation This parameter is active when option
*
5-22 Terminal X46/5 Digital Input
Option:
[0]
No operation This parameter is active when option
*
72
FC 300 Programming Guide
No.
PTC
[0]
-
-
[3]
-
[4]
PTC 1 Safe Stop
[A71]
[5]
PTC 1 Safe Stop
[W71]
PTC 1 Safe Stop
[A71]
PTC 1 Safe Stop
[W71]
[8]
PTC 1 Safe Stop
[A71]
[9]
PTC 1 Safe Stop
[W71]
Function:
MCB 113 is installed in the frequency convert-
er. Functions are described under 5-1* Digital
Inputs
Function:
moduleMCB 113 is installed in the frequency
converter. Functions are described under 5-1*
Digital Inputs
Function:
moduleMCB 113 is installed in the frequency
converter. Functions are described under 5-1*
Digital Inputs
MG.33.M9.02 - VLT
5-23 Terminal X46/7 Digital Input
Option:
[0]
No operation This parameter is active when option
*
Relay
-
5-24 Terminal X46/9 Digital Input
Safe Stop [A68]
Option:
Safe Stop [W68]
[0]
No operation This parameter is active when option module
*
-
-
5-25 Terminal X46/11 Digital Input
Safe Stop [A68]
Option:
[0]
No operation This parameter is active when option
*
Safe Stop [W68]
Safe Stop [W68]
5-26 Terminal X46/13 Digital Input
Safe Stop [A68]
Option:
[0]
No operation This parameter is active when option module
*
3.7.3 5-3* Digital Outputs
The 2 solid-state digital outputs are common for terminals 27
and 29. Set the I/O function for terminal 27 in
par. 5-01 Terminal 27 Mode, and set the I/O function for
terminal 29 in par. 5-02 Terminal 29 Mode. These parameters
cannot be adjusted while the motor is running.
[0]
No operation
[1]
Control ready
[2]
Drive ready
[3]
Drive ready /
remote
control
[4]
Enable / no
warning
[5]
VLT running
[6]
Running / no
warning
®
is a registered Danfoss trademark
Function:
moduleMCB 113 is installed in the frequency
converter. Functions are described under 5-1*
Digital Inputs
Function:
MCB 113 is installed in the frequency convert-
er. Functions are described under 5-1* Digital
Inputs
Function:
moduleMCB 113 is installed in the frequency
converter. Functions are described under 5-1*
Digital Inputs
Function:
MCB 113 is installed in the frequency convert-
er. Functions are described under 5-1* Digital
Inputs
Default for all digital outputs and relay
outputs
The control card is ready. E.g.: Feedback
from a drive where the control is supplied
by an external 24 V (MCB 107) and the main
power to drive is not detected.
The frequency converter is ready for
operation and applies a supply signal on the
control board.
The frequency converter is ready for
operation and is in Auto On mode.
Ready for operation. No start or stop
command is been given (start/disable). No
warnings are active.
Motor is running and shaft torque present.
Output speed is higher than the speed set in
par. 1-81 Min Speed for Function at Stop
[RPM]. The motor is running and there are
no warnings.