Parameter Descriptions
1-55 U/f Characteristic - U
Range:
Application
dependent
1000.0 V]
*
3
3
1-56 U/f Characteristic - F
Range:
Application
dependent
tion
*
dependant]
1-58 Flystart Test Pulses Current
Range:
30 %
[0 - 200
*
%]
40
Function:
[0.0 -
Enter the voltage at each frequency
point to manually form a U/f character-
istic matching the motor.
The frequency points are defined in
par. 1-56 U/f Characteristic - F.
This parameter is an array parameter
[0-5] and is only accessible when
par. 1-01 Motor Control Principle is set to
U/f [0].
Function:
[Applica-
Enter the frequency points to manual-
ly form a U/f-characteristic matching
the motor.
The voltage at each point is defined in
par. 1-55 U/f Characteristic - U.
This parameter is an array parameter
[0-5] and is only accessible when
par. 1-01 Motor Control Principle is set
to U/f [0].
Function:
Control the percentage of the magnetizing
current for the pulses used to detect the motor
direction. Reducing this value will reduce the
generated torque. 100% means nominal motor
current. The parameter is active when
par. 1-73 Flying Start is enabled. This parameter
plus
is only available in VVC
.
MG.33.M9.02 - VLT
FC 300 Programming Guide
1-59 Flystart Test Pulses Frequency
Range:
200 %
*
%]
3.3.6 1-6* Load Depend. Setting
1-60 Low Speed Load Compensation
Range:
100 %
*
%]
Motor size
0.25 kW - 7.5 kW
1-61 High Speed Load Compensation
Range:
100 %
*
%]
Motor size
0.25 kW - 7.5 kW
®
is a registered Danfoss trademark
Function:
[0 - 500
Control the percentage of the frequency for the
pulses used to detect the motor direction.
Increasing this value will reduce the generated
torque. 100% means 2 times the slip frequency.
The parameter is active when par. 1-73 Flying
Start is enabled. This parameter is only available
plus
in VVC
.
Function:
[0 - 300
Enter the % value to compensate voltage in
relation to load when the motor is running at
low speed and obtain the optimum U/f
characteristic. The motor size determines the
frequency range within which this parameter
is active.
Change over
< 10 Hz
Function:
[0 - 300
Enter the % value to compensate voltage in
relation to load when the motor is running at
high speed and obtain the optimum U/f
characteristic. The motor size determines the
frequency range within which this parameter
is active.
Change-over
> 10 Hz