Parameter Descriptions
0-12 This Set-up Linked to
Option:
3
3
[0]
Not
*
linked
[1]
Set-up 1
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
26
FC 300 Programming Guide
Function:
1. Change the edit set-up to Set-up 2 [2] in
par. 0-11 Edit Set-up and set par. 0-12 This Set-up
Linked to to Set-up 1 [1]. This will start the linking
(synchronising) process.
OR
2. While still in Set-up 1, copy Set-up 1 to Set-up
2. Then set par. 0-12 This Set-up Linked to to Set-up
2 [2]. This will start the linking process.
After the link is complete, par. 0-13 Readout:
Linked Set-ups will read {1,2} to indicate that all
'not changeable during operation' parameters are
now the same in Set-up 1 and Set-up 2. If there
are changes to a 'not changeable during
operation' parameter, e.g. par. 1-30 Stator Resist-
ance (Rs), in Set-up 2, they will also be changed
automatically in Set-up 1. A switch between Set-
up 1 and Set-up 2 during operation is now
possible.
MG.33.M9.02 - VLT
0-13 Readout: Linked Set-ups
Array [5]
Range:
Function:
0
[0 -
View a list of all the set-ups linked by means of
N/
255
par. 0-12 This Set-up Linked to. The parameter has one
A
N/
index for each parameter set-up. The parameter value
*
A]
displayed for each index represents which setups are
linked to that parameter setup.
Index
0
1
2
3
4
Table 3.2: Example: Set-up 1 and Set-up 2 are linked
0-14 Readout: Edit Set-ups / Channel
Range:
Function:
0
[-2147483648 -
View the setting of par. 0-11 Edit Set-up for
*
2147483647 ]
each of the four different communication
channels. When the number is displayed in
hex, as it is in the LCP, each number
represents one channel.
Numbers 1-4 represent a set-up number; 'F'
means factory setting; and 'A' means active
set-up. The channels are, from right to left:
LCP, FC-bus, USB, HPFB1-5.
Example: The number AAAAAA21h means
that the FC bus selected Set-up 2 in
par. 0-11 Edit Set-up, the LCP selected Set-up
1 and all others used the active set-up.
®
is a registered Danfoss trademark
LCP value
{0}
{1,2}
{1,2}
{3}
{4}

Advertisement