Danfoss FC 300 Programming Manual page 129

Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

Parameter Descriptions
13-40 Logic Rule Boolean 1
Array [6]
Option:
Function:
[74] SL Time-out 7
[75] Start command given
[76] Digital input x30/2
[77] Digital input x30/3
[78] Digital input x30/4
[79] Digital input x46/1
[80] Digital input x46/3
[81] Digital input x46/5
[82] Digital input x46/7
[83] Digital input x46/9
[84] Digital input x46/11
[85] Digital input x46/13
13-41 Logic Rule Operator 1
Array [6]
Option:
Function:
Select the first logical operator to use on the
Boolean inputs from par. 13-40 Logic Rule
Boolean 1 and par. 13-42 Logic Rule Boolean
2.
[13 -XX] signifies the boolean input of par.
group 13-*.
[0]
DISABLED
Ignores par. 13-42 Logic Rule Boolean 2,
*
par. 13-43 Logic Rule Operator 2, and
par. 13-44 Logic Rule Boolean 3.
[1]
AND
Evaluates the expression [13-40] AND
[13-42].
[2]
OR
evaluates the expression [13-40] OR[13-42].
[3]
AND NOT
evaluates the expression [13-40] AND NOT
[13-42].
[4]
OR NOT
evaluates the expression [13-40] OR NOT
[13-42].
[5]
NOT AND
evaluates the expression NOT [13-40] AND
[13-42].
[6]
NOT OR
evaluates the expression NOT [13-40] OR
[13-42].
[7]
NOT AND NOT evaluates the expression NOT [13-40] AND
NOT [13-42].
[8]
NOT OR NOT
evaluates the expression NOT [13-40] OR
NOT [13-42].
FC 300 Programming Guide
13-42 Logic Rule Boolean 2
Array [6]
Option:
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10] Out of speed range
[11] Below speed low
[12] Above speed high
[13] Out of feedb. range
[14] Below feedb. low
[15] Above feedb. high
[16] Thermal warning
[17] Mains out of range
[18] Reversing
[19] Warning
[20] Alarm (trip)
[21] Alarm (trip lock)
[22] Comparator 0
[23] Comparator 1
[24] Comparator 2
[25] Comparator 3
[26] Logic rule 0
[27] Logic rule 1
[28] Logic rule 2
[29] Logic rule 3
[30] SL Time-out 0
[31] SL Time-out 1
[32] SL Time-out 2
[33] Digital input DI18
[34] Digital input DI19
[35] Digital input DI27
[36] Digital input DI29
[37] Digital input DI32
[38] Digital input DI33
[39] Start command
[40] Drive stopped
[41] Reset Trip
[42] Auto-reset Trip
[43] Ok key
[44] Reset key
[45] Left key
[46] Right key
®
MG.33.M9.02 - VLT
is a registered Danfoss trademark
Function:
False
Select the second boolean (TRUE or
*
FALSE) input for the selected logic
rule. See par. 13-01 Start Event ([0] -
[61]) and par. 13-02 Stop Event ([70] -
[75]) for further description.
True
Running
In range
On reference
Torque limit
Current limit
Out of current range
Below I low
Above I high
3
3
129