Parameter Descriptions
14-53 Fan Monitor
Option:
[0]
Disabled
3
3
[1]
Warning
*
[2]
Trip
14-55 Output Filter
Option:
[0]
No Filter
*
[1]
Sine-Wave Filter
[2]
Sine-Wave Filter
Fixed
14-56 Capacitance Output Filter
Compensation function of the LC-filter requires the per phase
equivalent star connected capacitance of the filter (3 times the
capacity between two phases when capacitance is 'Delta' connec-
tion).
Range:
2.0 uF
[0.1 - 6500.0 uF] Set the capacitance of the output filter.
*
14-57 Inductance Output Filter
Range:
7.000
[0.001 -
mH
65.000 mH]
*
140
FC 300 Programming Guide
Function:
Select which reaction the frequency converter
should take in case a fan fault is detected.
Function:
Select the type of output filter connec-
ted. This parameter cannot be
adjusted while motor is running.
Function:
The value can be found on the filter
label.
NOTE
This is required for correct
compensation in Flux mode
(par. 1-01 Motor Control Princi-
ple)
Function:
Set the inductance of the output filter.
The value can be found on the filter
label.
NOTE
This is required for correct
compensation in Flux mode
(par. 1-01 Motor Control Principle)
MG.33.M9.02 - VLT
3.15.7 14-7* Compatibility
The parameters in this group are for setting of compatibility
for VLT 3000, VLT 5000 to FC 300
14-72 VLT Alarm Word
Option:
Function:
[0] 0 - 4294967295 Read out the alarm word corresponding to
VLT 5000
14-73 VLT Warning Word
Option:
Function:
[0] 0 - 4294967295 Read out the warning word corresponding to
VLT 5000
14-74 Leg. Ext. Status Word
Range:
0
[0 - 4294967295 ] Read out the ext. status word correspond-
*
3.15.8 14-8* Options
14-80 Option Supplied by External 24VDC
Option:
Function:
[0]
No
Select No [0] to use the drive's 24 V DC supply.
[1]
Yes Select Yes [1] if an external 24 V DC supply will be used
*
to power the option. Inputs/Outputs will be galvanically
isolated from the drive when operated from an external
supply.
NOTE
This parameter is only changing function by performing
a power cycle.
14-89 Option Detection
Selects the behaviour of the frequency converter when a change in
the option configuration is detected.
Option:
[0]
Frozen Configura-
*
tion
[1]
Enable Option
Change
®
is a registered Danfoss trademark
Function:
ing to VLT 5000
Function:
Freezes the current settings and
prevents unwanted changes when
missing or defective options are
detected.
Changes drive settings and is used
when modifying the system configura-
tion. This Parameter setting will return
to [0] after an Option Change.