Parameter Descriptions
[63]
Comparator 3
[64]
Comparator 4
3
3
[65]
Comparator 5
[70]
Logic Rule 0
[71]
Logic Rule 1
[72]
Logic Rule 2
[73]
Logic Rule 3
[74]
Logic Rule 4
[75]
Logic Rule 5
[80]
SL Digital
Output A
[81]
SL Digital
Output B
[82]
SL Digital
Output C
[83]
SL Digital
Output D
[84]
SL Digital
Output E
74
FC 300 Programming Guide
See par. group 13-1*. If Comparator 3 is
evaluated as TRUE, the output will go high.
Otherwise, it will be low.
See par. group 13-1*. If Comparator 4 is
evaluated as TRUE, the output will go high.
Otherwise, it will be low.
See par. group 13-1*. If Comparator 5 is
evaluated as TRUE, the output will go high.
Otherwise, it will be low.
See par. group 13-4*. If Logic Rule 0 is
evaluated as TRUE, the output will go high.
Otherwise, it will be low.
See par. group 13-4*. If Logic Rule 1 is
evaluated as TRUE, the output will go high.
Otherwise, it will be low.
See par. group 13-4*. If Logic Rule 2 is
evaluated as TRUE, the output will go high.
Otherwise, it will be low.
See par. group 13-4*. If Logic Rule 3 is
evaluated as TRUE, the output will go high.
Otherwise, it will be low.
See par. group 13-4*. If Logic Rule 4 is
evaluated as TRUE, the output will go high.
Otherwise, it will be low.
See par. group 13-4*. If Logic Rule 5 is
evaluated as TRUE, the output will go high.
Otherwise, it will be low.
See par. 13-52 SL Controller Action. The
output will go high whenever the Smart
Logic Action [38] Set dig. out. A high is
executed. The output will go low whenever
the Smart Logic Action [32] Set dig. out. A
low is executed.
See par. 13-52 SL Controller Action. The input
will go high whenever the Smart Logic
Action [39] Set dig. out. A high is executed.
The input will go low whenever the Smart
Logic Action [33] Set dig. out. A low is
executed.
See par. 13-52 SL Controller Action. The input
will go high whenever the Smart Logic
Action [40] Set dig. out. A high is executed.
The input will go low whenever the Smart
Logic Action [34] Set dig. out. A low is
executed.
See par. 13-52 SL Controller Action. The input
will go high whenever the Smart Logic
Action [41] Set dig. out. A high is executed.
The input will go low whenever the Smart
Logic Action [35] Set dig. out. A low is
executed.
See par. 13-52 SL Controller Action. The input
will go high whenever the Smart Logic
Action [42] Set dig. out. A high is executed.
The input will go low whenever the Smart
Logic Action [36] Set dig. out. A low is
executed.
MG.33.M9.02 - VLT
[85]
SL Digital
See par. 13-52 SL Controller Action. The input
Output F
will go high whenever the Smart Logic
Action [43] Set dig. out. A high is executed.
The input will go low whenever the Smart
Logic Action [37] Set dig. out. A low is
executed.
[120] Local
Output is high when par. 3-13 Reference Site
reference
= [2] Local or when par. 3-13 Reference Site =
active
[0] Linked to hand auto at the same time as
the LCP is in Hand on mode.
[121] Remote
Output is high when par. 3-13 Reference Site
reference
= Remote [1] or Linked to hand/auto [0] while
active
the LCP is in [Auto on] mode. See above.
[122] No alarm
Output is high when no alarm is present.
[123] Start
Output is high when there is an active Start
command
command (i.e. via digital input bus connec-
active
tion or [Hand on] or [Auto on]), and no Stop
or Start command is active.
[124] Running
Output is high when the frequency convert-
reverse
er is running counter clockwise (the logical
product of the status bits 'running' AND
'reverse').
[125] Drive in hand
Output is high when the frequency convert-
mode
er is in Hand on mode (as indicated by the
LED light above [Hand on]).
[126] Drive in auto
Output is high when the frequency convert-
mode
er is in Hand on mode (as indicated by the
LED light above [Auto on]).
5-30 Terminal 27 Digital Output
Option:
Function:
[0]
No operation Functions are described under 5-3* Digital
*
Outputs
®
is a registered Danfoss trademark
Reference site set
Local
Remote
in
referenc
reference
par. 3-13 Reference
e
active [121]
Site
active
[120]
Reference site:
1
Local
par. 3-13 Reference
Site [2]
Reference site:
0
Remote
par. 3-13 Reference
Site [1]
Reference site:
Linked to Hand/
Auto
Hand
1
Hand -> off
1
Auto -> off
0
Auto
0
0
1
0
0
0
1