Parameter Descriptions
9-71 Profibus Save Data Values
Option:
Function:
Parameter values changed via Profibus are not
automatically stored in non-volatile memory. Use
this parameter to activate a function that stores
parameter values in the EEPROM non-volatile
memory, so changed parameter values will be
retained at power-down.
[0]
Off
Deactivates the non-volatile storage function.
*
[1]
Store all
Stores all parameter values for all set-ups in the
setups
non-volatile memory. The selection returns to Off
[0] when all parameter values have been stored.
[2]
Store all
Stores all parameter values for all set-ups in the
setups
non-volatile memory. The selection returns to Off
[0] when all parameter values have been stored.
9-72 ProfibusDriveReset
Option:
Function:
[0]
No action
*
[1]
Power-on
Resets frequency converter upon power-up, as
reset
for power-cycle.
[3]
Comm
Resets the Profibus option only, useful after
option reset
changing certain settings in par. group 9-**,
e.g. par. 9-18 Node Address.
When reset, the frequency converter
disappears from the fieldbus, which may
cause a communication error from the master.
9-75 DO Identification
Range:
Function:
0
[0 - 65535 ] Provides information about the DO (Drive
*
Object).
9-80 Defined Parameters (1)
Array [116]
No LCP access
Read only
Range:
Function:
0 N/A
[0 - 9999 N/A] This parameter displays a list of all the
*
defined frequency converter parameters
available for Profibus.
9-81 Defined Parameters (2)
Array [116]
No LCP access
Read only
Range:
Function:
0 N/A
[0 - 9999 N/A] This parameter displays a list of all the
*
defined frequency converter parameters
available for Profibus.
FC 300 Programming Guide
9-82 Defined Parameters (3)
Array [116]
No LCP access
Read only
Range:
0 N/A
9-83 Defined Parameters (4)
Array [116]
No LCP access
Read only
Range:
0 N/A
9-84 Defined Parameters (5)
Range:
0
*
9-90 Changed Parameters (1)
Array [116]
No LCP access
Read only
Range:
0 N/A
9-91 Changed Parameters (2)
Array [116]
No LCP access
Read only
Range:
0 N/A
9-92 Changed Parameters (3)
Array [116]
No LCP access
Read only
Range:
0 N/A
®
MG.33.M9.02 - VLT
is a registered Danfoss trademark
Function:
[0 - 9999 N/A] This parameter displays a list of all the
*
defined frequency converter parameters
available for Profibus.
Function:
[0 - 9999 N/A] This parameter displays a list of all the
*
defined frequency converter parameters
available for Profibus.
Function:
[0 - 9999 ] This parameter displays a list of all the defined
frequency converter parameters available for
Profibus.
Function:
[0 - 9999 N/A] This parameter displays a list of all the
*
frequency converter parameters deviat-
ing from default setting.
Function:
[0 - 9999 N/A] This parameter displays a list of all the
*
frequency converter parameters deviat-
ing from default setting.
Function:
[0 - 9999 N/A] This parameter displays a list of all the
*
frequency converter parameters deviat-
ing from default setting.