Parameter Descriptions
15-10 Logging Source
Array [4]
Option:
[1660] Digital Input
[1662] Analog Input 53
[1664] Analog Input 54
[1665] Analog Output 42 [mA]
[1666] Digital Output [bin]
[1675] Analog In X30/11
[1676] Analog In X30/12
[1677] Analog Out X30/8 [mA]
[1690] Alarm Word
[1692] Warning Word
[1694] Ext. Status Word
[1860] Digital Input 2
[3110] Bypass Status Word
[3470] MCO Alarm Word 1
[3471] MCO Alarm Word 2
15-11 Logging Interval
Range:
Application
[Application
dependent
dependant]
*
15-12 Trigger Event
Select the trigger event. When the trigger event occurs, a window
is applied to freeze the log. The log will then retain a specified
percentage of samples before the occurrence of the trigger event
(par. 15-14 Samples Before Trigger).
Option:
[0]
False
*
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current limit
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[10]
Out of speed range
[11]
Below speed low
[12]
Above speed high
[13]
Out of feedb. range
[14]
Below feedb. low
[15]
Above feedb. high
[16]
Thermal warning
[17]
Mains out of range
[18]
Reversing
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip lock)
[22]
Comparator 0
FC 300 Programming Guide
Function:
Function:
Enter the interval in millisec-
onds between each sampling
of the variables to be logged.
Function:
®
MG.33.M9.02 - VLT
is a registered Danfoss trademark
15-12 Trigger Event
Select the trigger event. When the trigger event occurs, a window
is applied to freeze the log. The log will then retain a specified
percentage of samples before the occurrence of the trigger event
(par. 15-14 Samples Before Trigger).
Option:
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
[26]
Logic rule 0
[27]
Logic rule 1
[28]
Logic rule 2
[29]
Logic rule 3
[33]
Digital input DI18
[34]
Digital input DI19
[35]
Digital input DI27
[36]
Digital input DI29
[37]
Digital input DI32
[38]
Digital input DI33
[50]
Comparator 4
[51]
Comparator 5
[60]
Logic rule 4
[61]
Logic rule 5
15-13 Logging Mode
Option:
Function:
[0]
Log always
Select Log always [0] for continuous logging.
*
[1]
Log once on
Select Log once on trigger [1] to conditionally
trigger
start and stop logging using
par. 15-12 Trigger Event and
par. 15-14 Samples Before Trigger.
15-14 Samples Before Trigger
Range:
Function:
50
[0 - 100 ] Enter the percentage of all samples prior to a
*
trigger event which are to be retained in the log.
See also par. 15-12 Trigger Event and
par. 15-13 Logging Mode.
3
3
Function:
143