Parameter Descriptions
12-94 Broadcast Storm Protection
Option:
Function:
The built-in switch is capable of protecting the
switch system from receiving too many
broadcast packages, which can use up network
resources. The value indicates a percentage of
the total bandwidth that is allowed for
broadcast messages.
Example:
The "OFF" means that the filter is disabled –all
broadcast messages will be passed through.
The value "0%" means that no broadcast
messages will be passed through. A value of
"10%" means that 10% of the total bandwidth is
allowed for broadcast messages, if the amount
of broadcast messages increases above the 10%
threshold, they will be blocked.
[0] Protection
Value Port 1
(*Off – 20%)
[1] Protection
Value Port 2
(*Off – 20%)
12-95 Broadcast Storm Filter
Option:
Function:
Applies to par. 12-94; if the Broadcast
Storm Protection should also include
Multicast telegrams.
[0] Broadcast only
[1] Broadcast & Multicast
12-96 Port Mirroring
Enables/disables port-mirroring function. For troubleshooting with
a network analyzer tool.
Option:
[0]
Disable
*
[1]
Port 1 to Port 2
[2]
Port 2 to Port 1
[254]
Int. Port to Port 1
[255]
Int. Port to Port 2
FC 300 Programming Guide
Function:
No port-mirroring
All network traffic on port 1 will
be mirrored to port 2.
All network traffic on port 2 will
be mirrored to port 1.
®
MG.33.M9.02 - VLT
is a registered Danfoss trademark
12-98 Interface Counters
Option:
Function:
Read only. Advanced Interface
counters, from build-in switch, can
be used for low-level trouble-
shooting, The parameter shows a
sum of port 1 + port 2.
[0]
In Octets
[1]
In Unicast Packets
[2]
In Non-Unicast Packets
[3]
In Discards
[4]
In Errors
[5]
In Unknown Protocols
[6]
Out Octets
[7]
Out Unicast Packets
[8]
Out Non-Unicast Packets
[9]
Out Discards
[10] Out Errors
12-99 Media Counters
Option:
Function:
Read only. Advanced Interface
counters, from build-in switch, can be
used for low-level trouble-shooting,
The parameter shows a sum of port 1 +
port 2.
[0]
Alignment Errors
[1]
FCS Errors
[2]
Single Collisions
[3]
Multiple Collisions
[4]
SQE Test Errors
[5]
Deferred Errors
[6]
Late Collisions
[7]
Excessive Collisions
[8]
MAC Transmit Errors
[9]
Carrier Sense Errors
[10] Frame Too Long
[11] MAC Receive Errors