Danfoss FC 300 Programming Manual page 96

Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

Parameter Descriptions
7-07 Speed PID Feedback Gear Ratio
Range:
1.0000
[Application dependant]
*
3
3
7-08 Speed PID Feed Forward Factor
Range:
0 %
[0 - 500 %] The reference signal bypasses the speed
*
3.9.2 7-1* Torque PI Control
Parameters for configuring the torque PI control in torque
open loop (par. 1-00 Configuration Mode).
7-12 Torque PI Proportional Gain
Range:
100 %
[0 - 500 %] Enter the proportional gain value for the
*
7-13 Torque PI Integration Time
Range:
0.020 s
[0.002 - 2.000
*
s]
3.9.3 7-2* Process Ctrl. Feedb.
Select the feedback sources for the Process PID Control, and
how this feedback should be handled.
7-20 Process CL Feedback 1 Resource
Option:
96
FC 300 Programming Guide
Function:
Function:
controller by the amount specified. This
feature increases the dynamic performance of
the speed control loop.
Function:
torque controller. Selection of a high value
makes the controller react faster. Too high a
setting leads to controller instability.
Function:
Enter the integration time for the torque
controller. Selection of a low value
makes the controller react faster. Too
low a setting leads to control instability.
Function:
The effective feedback signal is made
up of the sum of up to two different
input signals.
Select which frequency converter
input should be treated as the source
MG.33.M9.02 - VLT
7-20 Process CL Feedback 1 Resource
Option:
[0]
No function
*
[1]
Analog input 53
[2]
Analog input 54
[3]
Frequency input 29
[4]
Frequency input 33
[7]
Analog input X30/11
[8]
Analog input X30/12
[15] Analog Input X48/2
7-22 Process CL Feedback 2 Resource
Option:
[0]
No function
*
[1]
Analog input 53
[2]
Analog input 54
[3]
Frequency input 29
[4]
Frequency input 33
[7]
Analog input X30/11
[8]
Analog input X30/12
[15] Analog Input X48/2
3.9.4 7-3* Process PID Ctrl.
7-30 Process PID Normal/ Inverse Control
Option:
Function:
Normal and inverse control are implemented by
introducing a difference between the reference
signal and the feedback signal.
[0]
Normal Sets process control to increase the output frequen-
*
cy.
[1]
Inverse Sets process control to reduce the output frequency.
7-31 Process PID Anti Windup
Option:
Function:
[0]
Off Ceases regulation of an error when the output frequency
can no longer be adjusted.
[1]
On Continues regulation of an error even when the output
*
frequency cannot be increased or decreased.
®
is a registered Danfoss trademark
Function:
of the first of these signals. The second
input signal is defined in
par. 7-22 Process CL Feedback 2
Resource.
Function:
The effective feedback signal is made
up of the sum of up to two different
input signals. Select which frequency
converter input should be treated as
the source of the second of these
signals. The first input signal is defined
in par. 7-21.