Page 1
Effective August 2019 PowerXL DH1 Series VFD Supersedes February 2019 Application manual Supports Firmware Version Bundle: DH1-V0005-ETN...
Page 2
CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability, or otherwise for any special, indirect, incidental, or consequential damage or loss whatsoever, including but not limited to damage or loss...
Page 3
PowerXL DH1 series variable frequency drives Support services Support services The goal of Eaton is to ensure your greatest possible satisfaction with the operation of our products. We are dedicated to providing fast, friendly, and accurate assistance. That is why we offer you so many ways to get the support you need.
Fit appropriate warning signs This should not cause dangerous operating states even for POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Disconnect power before checking controllers or performing maintenance. Be sure equipment is properly grounded. Wear safety glasses whenever working on electronic controllers or rotating machinery. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Do not touch the components on the circuit boards. Static voltage discharge may damage the components. WARNING Check that the EMC level of the AC drive corresponds to the requirements of your supply network. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com xvii...
Page 18
Do not perform any voltage withstand tests on any part of PowerXL Series Drive. There is a certain procedure according to which the tests shall be performed. Ignoring this procedure may result in damaged product. xviii POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 19
Les dispositifs d’arrêt d’urgence conformes à la • norme CEI/EN 60204-1 doivent être efficace dans tous les modes de fonctionnement des dispositifs d’automatisation. Le déverrouillage des dispositifs d’arrêt d’urgence ne doit pas entraîner un redémarrage POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 20
MISE EN GARDE peut, si elle n’est pas évitée, entraîner des conséquences graves. Des mesures de sécurité importantes sont décrites dans les MISES EN GARDE (ainsi que dans les AVERTISSEMENTS). POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 21
à d’éventuelles défaillances électriques. Le non-respect de cette précaution peut entraîner la mort ou des blessures graves. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 22
MISE EN GARDE conducteur en cuivre doit être utilisé avec cet entraînement. Installer cet entraînement sur une matière résistante aux flammes, telle qu’une plaque d’acier, pour réduire les risques d’incendie. xxii POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 23
à la terre pour ne pas endommager l’entraînement dommages potentiels. ote: Lorsque le filtre CEM interne est débranché, l’entraînement peut ne pas être conforme aux normes de compatibilité électromagnétique. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com xxiii...
Page 24
CA réglable Le non-respect de ces instructions peut entraîner des blessures ou des dégâts matériels. Pour plus d’informations techniques, contacter l’usine ou le représentant commercial Eaton local. xxiv POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
PowerXL Series VFD on the Low overload current (110%) wall or in a cabinet. Variable Frequency Drive Real Time Clock POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
261 = 261A, 200HP, 132KW 310 = 310A, 250HP, 160KW IP00 FR7 and FR8 is not avaliable for 230V input product or with the PowerXL DH1 Product IP20 FR0 will be avalible in June 2018 POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Increase Value Scroll Menu Up Auto Control Place Select Move Cursor Right Back/Reset Button Start /Hand Button Stop/Off Button Move Cursor Left Enter Menu Decrease Value Confirm Selection Scroll Menu Down POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
In parameter comparison mode, scroll through the parameters of which current value is • different from comparison parameter value. In parameter page when in read mode, move to the previous or next brother parameter of • this parameter. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 34
When Keypad is the reference place after hitting the start button, it will jump directly to the Keypad Ref Screen. Places drive into Hand Control place. Hitting start again if keypad is the control location will start the Drive. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Selection LCD shall show the welcome page when power on. See Figure 7. Figure 7. Welcome page Real Time Clock (hh:mm) Soft Key 1 Soft Key 2 Function Label Function Label POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
No Action be shown on the left. Otherwise, it will not be shown. See Figure 10 Upload to keypad Figure 10. Main menu 13:53 S: Startup Wizard M: Monitor P: Parameter BYPASS 13:53 POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
0.00 Hz F - Fault F1 – Active Fault F2 – History Fault F3 – Fault Log B – Optional Boards T- Favorite O – Operate Mode S – Startup Wizard POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
R13 - PID1 Keypad Set Point 2 P10 - Bypass Startup Wizard S - Startup Wizard P11 - Real Time Clock P12 - Communictions P13 - System ote: Will vary depending on application selected POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
In pop-up faults page, it returns to the last page. Pressing the back/reset key more than 2 seconds shall reset all active faults when all the active fault condition is not satisfied. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Total Power Day Count: 0 Operation Hours: 13 13:53 MENU F1: Active Fault No Fault F2: HistoryFault Right/OK key No Active Fault F3: Fault Log BYPASS 13:53 REVERSE BYPASS 13:53 REVERSE POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
2, Store Set 1, Store Set 2, Reset, Reload Defaults VM. The Drive shall restart after default parameters are loaded • special points are: “Reload Defaults VM” is for the sales stand. Do not use • on a fully functioning drive POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Up Key Up key P13.1.5 P13.1.5 Down from Keypad Down from Keypad All, No Motor All Parameters … BYPASS 13:53 FAVORITE BYPASS 13:53 FAVORITE Ok Key P13.1.5 Down from Keypad Waiting... 13:53 POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Current Value in Drive 13:53 13:53 Right key Allows changing Fan Control Fan Control Continous Continous Up Key Temperature Continous 13:53 13:53 Down Key Down Key Backlight Time 2 min 1 min 13:53 POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Up key P2.2.4 P2.4.2 AI1 Signal Range Password? OK key Password right 0-100% 0001 BYPASS 13:53 FAVORITE BYPASS 13:53 FAVOIRTE OK key Password wrong P2.4.2 After 3s Password? Failed BYPASS 13:53 FAVORITE POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Left key 0.01Hz 0.01Hz 0.00Hz BYPASS 13:53 FAVORITE BYPASS 13:53 FAVORITE BYPASS 13:53 FAVORITE Up key 9 times P1.1 P1.1 Min Frequency Min Frequency 0.10Hz 0.00Hz BYPASS 13:53 FAVORITE BYPASS 13:53 FAVORITE POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
(see Figure 12 on Page 13). After one parameter is removed from favorite list, the next parameter in the favorite list will be selected by default. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Now the Startup Wizard is done. It will not show again at the next power up. If you want to reset it, please select it from the main menu (“Startup Wizard”). POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Volts per Hertz control programmable • Real time clock—RTC time display • Auto restart on fault to drive or bypass • Programmable switching frequency • Multi-Preset speeds • Fan control • DC brake • POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
If we set Run Enable to DigIN:TimeChannel1 the drive will be enabled when the timer assigned to Time Channel 1 is active or High, and would not be enabled when the Time Channel is inactive or Low. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
When using the +10 V for AI1, it is important to wire AI1—ground (as shown by dashed line). If using +10 V for AI1 or AI2, terminals 3, 5, and 6 need to be jumpered together. AI1+ and AI2+ Support 10K potentiometer. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Bit 12 = RunEnable Bit 13 = Run Bypass Bit 14 = External Brake Control Bit 15 = In Bypass Mode Parameter value will be set to be default when changing macros. ote: POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Total Run Time Count 2827 M9.8 Number of Starts 2830 M9.9 Trip Run Time Count 2829 Table 25. Multi-Monitoring — M11 Code Parameter Min. Max. Unit Default Note M11.1 Multi-Monitoring 1,2,3 POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
AI Ref Scale Max Value See Par ID 144 400.00 0.00 Note: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Parameter value will be set to be default when changing macros. Input function is Level sensed. Input function is edge sensed. Input function is edge sensed when using StartP/StopP start logic. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 62
Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. Input function is edge sensed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
See Par ID 184 100.00 100.00 P2.5.5 AI2 Filter Time 0.00 10.00 0.10 P2.5.6 AI2 Signal Invert See Par ID 181 otes: Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
P3.1.5 RO2 Function See Par ID 151 P3.1.6 RO2 On Delay 320.0 2114 P3.1.7 RO2 Off Delay 320.0 2115 otes: Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
P3.2.31 Second AI Limit Supv Val 0.00 100.00 0.00 2195 P3.2.32 Second AI Supv Hyst 1.00 10.00 1.00 2199 otes: Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
0 = Disabled 1 = Enabled P4.1.6 Change PhaseSequence 2515 0 = Change Disable Motor 1 = Change Enable otes: Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
7 = kr P4.4.2 Energy Cost Varies 0.00 2123 otes: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
See Par ID 102 25.00 P6.1.10 Underload Protection P6.1.11 otes: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 69
20.0 2162 P6.1.21 Preheat Output Volt 20.0 2163 otes: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
33 = SlotA PT100 Temp Channel 2 34 = SlotA PT100 Temp Channel 3 otes: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Fire Mode Test Enable 2443 See Par ID 1679 otes: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
FB Process Data Input 8 Sel 2560 2540 otes: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
61 = Bypass Overload 62 = Bypass Run otes: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
See Par ID 2516 P12.3.3.8 MSTP Max Master 1537 otes: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
See Par ID 2516 P12.4.3.9 BACnetIP Instance Number 4194302 Varies 1742 otes: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
7 = l/h 8 = kg/s 9 = kg/min otes: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Power Unit Serial Number 1270 P13.3.5 Control Unit Serial Number 1276 otes: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Freq Reference Motor Speed Motor Current Motor Torque Motor Power Motor Voltage DC-link Voltage Unit Temperature °C Motor Temperature Keypad Reference See Par ID 101 See Par ID 102 Hz 0.00 POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Two independent set of Acceleration/Deceleration ramps • slot it is located in. Skip frequency • POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
If we set Run Enable to DigIN:6 the drive will be enabled when digital input 6 (Terminal 8) is closed, and would not be enabled when digital input 6 (Terminal 8) is open. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
When using the +10 V for AI1, it is important to wire AI1—ground (as shown by dashed line). If using +10 V for AI1 or AI2, terminals 3, 5, and 6 need to be jumpered together. AI1+ and AI2+ Support 10K potentiometer. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Min = Minimum value of parameter Max = Maximum value of parameter Unit = Unit of parameter value; given if available Default = Value preset by factory ID = ID number of the parameter POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Code Parameter Min. Max. Unit Default Note M3.1 PT100 Temperture °C 1000.0 Table 65. Energy Savings — M4 Code Parameter Min. Max. Unit Default Note M4.1 Energy Savings Varies 0.000 2120 POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Bit 14 = IO5_AC6 Bit 15 = Not Used ote: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
1 = Running 2 = Sleep Mode M6.6 PID2 Set Point Varies M6.7 PID2 Feedback Varies M6.8 PID2 Error Value Varies M6.9 PID2 Output M6.10 PID2 Status See Par ID 23 POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Total Run Time Count 2827 M9.8 Number of Starts 2830 M9.9 Trip Run Time Count 2829 Table 71. Multi-Monitoring — M11 Code Parameter Min. Max. Unit Default Note M11.1 Multi-Monitoring 1,2,3 POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
AI Ref Scale Max Value See Par ID 144 400.00 0.00 ote: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. Input function is edge sensed when using StartP/StopP start logic. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 89
OP Cont Interlock NO 2801 P2.2.49 OP Cont Interlock NC 2802 ote: Parameter value will be set to be default when changing macros. Input function is Level sensed. Input function is edge sensed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
See Par ID 181 ote: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
61 = Bypass Overload 62 = Bypass Run P3.1.2 RO1 Function See Par ID 151 P3.1.3 RO1 On Delay 320.0 2112 P3.1.4 RO1 Off Delay 320.0 2113 P3.1.5 RO2 Function See Par ID 151 POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
10.00 1.00 2199 ote: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
-100.00 100.00 0.00 ote: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Run Remove Stop Mode 2667 ote: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
3 = Linear + Flux Optimization ote: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
See Par ID 1346 ote: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 97
Preheat Output Volt 20.0 2163 ote: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
4 = Warning, Coast P6.3.2 OPTCard Fault Response See Par ID 308 P6.3.3 IP Address Confliction 1678 See Par ID 308 Resp P6.3.4 Keypad Comm Fault 2157 See Par ID 308 Response POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
39 = °F ote: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
PID1 Sleep Boost Max Time 2661 ote: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
200.00 0.00 1355 ote: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
200.00 100.00 1337 ote: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
300.00 0.00 1373 ote: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
200.00 0.00 1415 ote: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
200.00 100.00 1399 ote: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Smoke Purge Frequency 100.0 50.0 ote: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Redundant RunTime Limit 300000.0 2479 ote: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
See Par ID 519 ote: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
FB Process Data Input 8 Sel 2560 2540 ote: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
62 = Bypass Run ote: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
1 = in all Control ote: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
0x00.0x00. 0x00.0x00. 0x00.0x00 ote: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
See Par ID 625 ote: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 114
2460 P13.1.22 Output Display Unit Max See Par ID 2460 60000.00 Varies Varies 2425 P13.1.23 Keypad Lock Password 9999 ote: Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Varies 0.00 1309 ote: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Auto restart on fault to drive or bypass • Programmable switching frequency • Multi-Preset speeds • Fan control • Joystick Control • Logic Functions • Bumpless transition between Hand and Auto • Drooping • POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
6 is closed on the IO5 option card which is inserted in Slot A, and would not be enabled when digital input 6 on the option card is open. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
When using the +10 V for AI1, it is important to wire AI1—ground (as shown by dashed line). If using +10 V for AI1 or AI2, terminals 3, 5, and 6 need to be jumpered together. AI1+ and AI2+ Support 10K potentiometer. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Bit 11 = IO5_AC3 Bit 12 = IO5_AC4 Bit 13 = IO5_AC5 Bit 14 = IO5_AC6 Bit 15 = Not Used Note: Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
1 = Running 2 = Sleep Mode M6.6 PID2 Set Point Varies M6.7 PID2 Feedback Varies M6.8 PID2 Error Value Varies M6.9 PID2 Output M6.10 PID2 Status See Par ID 23 POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
1 = Keypad 2 = IO Terminal 3 = Fieldbus Note: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
AI Ref Scale Max Value See Par ID 144 400.00 0.00 Note: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. Input function is edge sensed when using StartP/StopP start logic. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 126
Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. Input function is Level sensed. Input function is edge sensed when using StartP/StopP start logic. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
AI2 Sleep Limit 0.00 100.00 0.00 P2.5.9 AI2 Sleep Delay 0.00 320.00 0.00 P2.5.10 AI2 Joystick Offset -50.00 50.00 0.00 Note: Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
58 = 2th Stage Ramp Frequency Active 59 = STO Fault Output 60 = Run Bypass/Drive 61 = Bypass Overload 62 = Bypass Run Note: Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Second AI Supv Select 2193 See Par ID 170 P3.2.30 Second AI Limit Supv 2194 See Par ID 154 Note: Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
37 = SlotB PT100 Temp Channel 2 38 = SlotB PT100 Temp Channel 3 39 = User Defined Output 40 = Motor Current (-2-+2N) ote: Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
34 = Un-Requested Rotation Direction 35 = Thermal Fault/Warning Note: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Run Remove Stop Mode 2667 See Par ID 253 Note: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
CurrCT*2 P5.1.3 V/Hz Optimization See Par ID 1346 Note: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
P6.1.16 PT100 Fault Response See Par ID 308 Note: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
0 = Start/Stop After Fault Reset 1 = Restart After Fault Reset Note: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Undervoltage Attempts OverVoltage Attempts P6.4.5 OverCurrent Attempts P6.4.6 Note: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
42 = HG 43 = ft 44 = m Note: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
2660 P7.3.1.5 PID1 Sleep Boost Max Time 2661 Note: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
PID1 Set Point 2 Comp Max -200.00 200.00 0.00 1355 Note: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
P7.5.1.2 PID1 Feedforward Gain -1000.0 1000.0 100.0 1339 Note: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
P8.1.11 PID2 Ramp Time 0.00 300.00 0.00 1373 Note: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
PID2 Set Point1 Comp Max -200.00 200.00 0.00 1415 Note: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
PID2 Feedback 2 Max -200.00 200.00 100.00 1399 Note: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
See Par ID 1346 P9.7 Smoke Purge Frequency 100.0 50.0 Note: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Interval 1 On Time P11.1.3 Interval 1 Off Time Note: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
P11.5.6 Interval 5 Channel See Par ID 519 Note: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
24 = Thermistor Fault Output 25 = Fire Mode Note: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
2 = 38400 3 = 57600 4 = 115200 Note: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Modbus TCP Trusted IP Enable P12.4.2.7 Trusted IP White List Note: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
1 = Change Disable P13.1.9 Multimonitor Set See Par ID 625 Note: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 151
See Par ID 2460 60000.00 Varies Varies 2425 P13.1.23 Keypad Lock Password Note: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Parameter value will be set to be default when changing macros. Input function is Level sensed. Input function is edge sensed. Input function is edge sensed when using StartP/StopP start logic. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
If a controlled run-down is requested (with value from ID104), stop mode should be set to ramp. When setting a minimum output frequency (ID104 greater than 0 Hz), the acceleration and deceleration time of the drive is reduced to t or t POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
• I/O terminal Start 1 and 2 would be from the Digital hardwired inputs assigned via the input group • Fieldbus would be from a communication bus. • Keypad would be from the Start/Stop buttons on the keypad. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 155
• I/O terminal Start 1 and 2 would be from the Digital hardwired inputs assigned via the input group • Fieldbus would be from a communication bus. • Keypad would be from the Start/Stop buttons on the keypad. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 156
AI Ref Scale Min Value 1,2,3 Min Frequency when min of Analog References is applied. With values set at 0 scaling will follow the minimum frequency value parameter Para ID 101. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
3 wire control with Start signal 2 required to be closed to enable Start on Start signal 1. 24V+ DIN1 ID190 - Start Signal: DigIN:1 ID143 Start Stop Logic: Start/Stop DIN2 ID191- Start Signal 2: DigIN:2 ID143 Start Stop Logic: Forward/Reverse POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
I/O Terminal 1 is the current control place. Can be set to DigiIN:X indicates on board terminal inputs, DigiIN:A:IOX:X indicates optional board inputs in A slot, DigiIN:B:IOX:X indicates optional board inputs in B slot, or Timer Channel X POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
When the DIN1 contact opens the direction of rotation starts to change. If Start forward (DIN1) and Start reverse (DIN2) signals are active simultaneously the Start forward signal (DIN1) has priority. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Para ID 143 = 3. Can be set to DigiIN:X indicates on board terminal inputs, DigiIN:A:IOX:X indicates optional board inputs in A slot, DigiIN:B:IOX:X indicates optional board inputs in B slot, or Timer Channel X Contact Open = Forward direction. Contact Close = Reverse direction. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 162
The description on the fault can be changed in parameter Para ID 2298. Closed contact = no external fault. Open contact = external fault. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 163
DigiIN:B:IOX:X indicates optional board inputs in B slot, or Timer Channel X. RO X Function allows for having an input turn on without having to hard wire it to the physical relay output. DI change from open contact to closed contact: reset fault. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Figure 36. Activation of fixed frequencies (Hz) 15 Hz 10 Hz 5 Hz 0 Hz POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 165
Function allows for having an input turn on without having to hard wire it to the physical relay output. Closed contact: remote2 is selected as control source. Open contact: remote1 is selected as control. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 166
DigiIN:B:IOX:X indicates optional board inputs in B slot, or Timer Channel X. RO X Function allows for having an input turn on without having to hard wire it to the physical relay output. Contact Close: Enables PID 1 control mode. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 167
Timer Channel X. RO X Function allows for having an input turn on without having to hard wire it to the physical relay output. Closed contact: drive output reference frequency selection 2 POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 168
Use this parameter to set the jogging speed set point, this speed is selected with the digital input programmed for Jogging speed. When enabled the drive starts and ramps to this speed, input removed drive stops. This parameter’s value is automatically limited between minimum and maximum frequency. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Figure 40. AI1 reference potentiometer 10V Standard I/O Board Terminal Signal 10V+ 10V supply AI1+ Analog input 1+ AI1- Analog input 1- AI2+ Analog input 2+ AI2- Analog input 2- I/O Ground 24Vo 24V auxillary voltage POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
A long filtering time makes the regulation response slower. Figure 42. AI1 signal filtering 100% P2.5 t (s) P2.15 P4.4 P4.11 otes: Analog signal with faults (unfiltered). Filtered analog signal. Filter time constant at 63% of the set value. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
10V supply AI1+ Analog input 1+ 2-wire Transmitter AI1- Analog input 1- Actual AI2+ Analog input 2+ − Value AI2- Analog input 2- I = (0)4...20mA I/O Ground 24Vo 24V auxillary voltage POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
AI12Custom Min <= AI2 Custom Max. P2.5.4 AI2 Custom Max 1,2,3 Defines the custom max range of the analog input scale when the signal range is set for custom. AI2 Custom Min <= AI2 Custom Max. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 174
This parameter defines the mid point of the analog joystick control. By moving the offset in a positive or negative direction will cause the min frequency crossing point to be move between +/-50% of the analog input scale. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 175
60 = Run Bypass/Drive - Run indication for drive and bypass. 61 = Bypass Overload - Bypass Overload fault input is enabled. 62 = Bypass Run - Drive run command for bypass is given POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 176
Use this parameter to set the delay time for RO1 relay to transition from logic 0 to 1 state. P3.1.4 2113 RO1 Off Delay 1,2,3 Use this parameter to set the delay time for RO1 relay to transition from logic 1 to 0 state. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 177
Use this parameter to set the delay time for RO2 relay to transition from logic 0 to 1 state. P3.1.7 2115 RO2 Off Delay 1,2,3 Use this parameter to set the delay time for RO2 relay to transition from logic 1 to 0 state. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 178
Use this parameter to invert the output logic of RO3 to be normally closed. Instead of normally open. Power off state of relay will be Normally Open. 1 = Not Inverted 2 = Inverted POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 179
60 = Run Bypass/Drive - Run indication for drive and bypass. 61 = Bypass Overload - Bypass Overload fault input is enabled. 62 = Bypass Run - Drive run command for bypass is given POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 180
It can also be used to enabled an external brake control relay. 0 = No supervision 1 = Low limit supervision 2 = High limit supervision 3 = Brake-on control POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
1,2,3 Use this parameter to define the hysteresis value between when the Torque supervision enables and disables itself. This value is in reference from distance away form the defined limit value. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 182
1,2,3 Use this parameter to define the hysteresis value between when the AI supervision enables and disables itself. This value is in reference from distance away form the defined limit value. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 183
1351 PID1 Superv Delay Use this parameter to set the delay time after which the PID feedback goes above or below the limit settings to provide status to relay output function. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Setting this parameter value to 0.00 will deactivate filtering. Figure 53. Analog output filtering 100% Notes P2.5 Analog signal with faults (unfiltered). P2.15 Filtered analog signal. P4.4 Filter time constant at 63% of the set value. P4.11 POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Use this parameter to define the signal minimum to be either 0 mA or 4 mA (AO1 mode = 0–20 mA); 0V or 2V (AO1 mode = 0–10V). 0 = Set minimum value to 0V/0 mA. 1 = Set minimum value to 2V/4 mA. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 186
Use this parameter for switching from local to remote mode, change reference only if changed in new source after switching, thus enabling use of ramps. Upon transition stopping can be performed via Keypad Stop, Enable input, ExtFault, or E-Stop. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
These parameters provide the possibility to set two different acceleration/ deceleration time sets for one application. The active set can be selected with the programmable digital input. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 188
Use this parameter to set the length of time the DC-brake is activated when the start command is given. P4.2.3 Stop DC-Brake Frequency 1,2,3 Use this parameter to set the frequency level in Hz at which DC braking starts during the deceleration phase. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
1 = Brake chopper in use and tested when running. Can be tested also in READY state. 2 = External brake chopper (no testing) 3 = Used and tested in READY state and when running 4 = Used when running (no testing) POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 190
Use this parameter to set frequency limits to prevent the drive from operating in, the frequency converter will skip the set frequencies, ramp time will be the same. In some systems it may be necessary to avoid certain frequencies because of mechanical resonance problems. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
This parameter determines the maximum motor current allowed from the frequency converter. When the motor current hits this level it goes into the current controller and tries to limit the output frequency to drop the current. This is not a fault trip limit. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Programmable V/Hz curve Figure 60. Linear and squared change of motor voltage U[V] Default: Nominal Field Weakening P8.5 Voltage of the Motor Point Linear Squared Default: Nominal Frequency of the Motor f [Hz] POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Use this parameter if programmable V/Hz curve has been selected,it defines the zero frequency voltage of the curve. When putting this value above 0% additional voltage is given, in some cases by putting this value to high it can cause the motor to be oversaturated. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 194
Use this parameter to set the device reaction to a “Phase Loss Output” condition. This failure could be device dependent. 0 = No response 1 = Warning 2 = Fault, stop mode after fault according to standard stop mode 3 = Fault, stop mode after fault always by coasting POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Setting this parameter does not affect the maximum output current of the drive, which is determined by Param ID1679 alone. Figure 62. Motor thermal current it curve Cooling Overload Area 100% P9.9 = 40% POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
The software does not allow entering a greater value than In-Motor*2. If nominal motor current is changed, this parameter is automatically restored to the default value (IL). Figure 64. Stall characteristics settings Stall Area P9.12 P9.14 POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
If you change Para ID486, nominal motor current, this parameter is automatically restored to the default value. Figure 66. Setting of minimum load Torque P9.16 P9.17 Underload Area 5 Hz Field Weakening Point P8.4 POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
PT100 sensor drops, this is typically used when the motor is not running. 0 = Disable 1 = Enable POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 199
3 = Do Not respond to I/O commands when power is applied. If in another control place and switched to I/O control the drive will respond to a maintained Run Command. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 200
2V level. This condition could be possible device dependent. 0 = No response 1 = Warning 2 = Fault, stop mode after fault according to standard stop mode 3 = Fault, stop mode after fault always by coasting POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 201
0 = No response 1 = Warning 2 = Fault, stop mode after fault according to standard stop mode. 3 = Fault, stop mode after fault always by coasting POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
0 = No automatic restart after overvoltage fault trip >0 = Number of automatic restarts after overvoltage fault trip. The fault is reset and the drive is started automatically after the DC-link voltage has returned to the normal level. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 203
This parameter defines the way the process value output reacts to the feedback signal. 0 = Normal, If feedback is less than set-point, PID controller output increases. 1 = Inverted, If feedback is less than set-point, PID controller output decreases. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 204
The output re engages when feedback rises above the wakeup level. When the function is disabled the drive will run at the minimum or maximum defined speed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 205
PID1 Set Point 2 Wake Up Level Use this parameter to set the level for the drive wakes up form the sleep mode condition. This level is variable based off the wake up action selection. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
The mathematical functions can be selected that is used when two feedback signals are combined. P7.4.1.2 1331 PID1 Feedback Gain Use this parameter to set the gain associated with feedback signal from the measuring signals defined in the feedback function. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 207
This parameter is used to defines the unit type for PID controller. This will change the Feedback and Setpoint variables to show the desired unit of measure. P8.1.5 1360 PID2 Process Unit Min This parameter is used to defines the minimum process unit value for the PID controller. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 208
PID2 Sleep boost level, range shall be [-9999,9999], unit shall be PID unit. Default value shall be 0. P8.3.1.5 2663 PID2 Sleep Boost Max Time PID2 Sleep boost maximum time, range shall be [1,300] seconds. Default value shall be 30s. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 209
The output re engages when feedback rises above the wakeup level. When the function is disabled the drive will run at the minimum or maximum defined speed. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 210
Use this parameter to enables pressure loss compensation for set point 2 signal value. This is used in pump systems to compensate the pressure loss that occurs at the end of the pipe line due to the liquid flow. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Use this parameter is used to select where feedback signal is being fed into the drive. This signal could be defined as analog inputs or fieldbus data value. P8.4.2.2 1395 PID2 Feedback 1 Min Use this parameter to set the minimum unit value for the feedback signal. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 212
Use this parameter to set the fire mode frequency reference 1 when the ref selection mode is used. P9.5 Fire Mode Freq Ref 2 1,2,3 Use this parameter to set the fire mode frequency reference 2 when the ref selection mode is used. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 213
This parameter specifies whether an automatic switch to bypass when an Charge Switch fault occurs. 0 = Disable Auto bypass on Charge Switch fault 1 = Enable Auto bypass on Charge Switch fault POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 214
Redundant Run Time Enable Use this parameter to enables the Run time limit for the Redundant drive mode so that drives will be cycled based off the Run time limit value. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 215
Interval 2 Off Time Use this parameter to set the off time for Interval function. It uses 24-hour format. Use to specify a time of day for a desired function to be disabled. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 216
Use this parameter to assign the interval to a select time channel to store the interval time. 0 = Not used 1 = Time channel 1 2 = Time channel 2 3 = Time channel 3 POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 217
Use this parameter to set the day of week for Interval function to start on. 0 = Sunday 1 = Monday 2 = Tuesday 3 = Wednesday 4 = Thursday 5 = Friday 6 = Saturday POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 218
Use this parameter to assign the Fieldbus Data Input Selections, parameter/monitor Para ID's can be assigned to these registers and then written over the desired Fieldbus Network Word for Process Data. see Communication Manual MN040010EN for more details. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 219
Process Data Out6 - Motor Voltage = ID 6 Process Data Out7 - DC Link Voltage = ID 7 Process Data Out8 - Active Fault Code = ID 28 see Communication Manual MN040010EN for more details. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 220
Use this parameter to select status indication of this bit2 to be read over the communication Standard Status Word. P12.2.12 2418 Standard Status Word Bit3 Function Select 1,2,3 Use this parameter to select status indication of this bit3 to be read over the communication Standard Status Word. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 221
MSTP Fault Code 1,2,3 Use this parameter to see the status of the BACnet Protocol faults 0 = None 1 = Sole Master 2 = Duplicate MAC ID 3 = Baud rate fault POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 222
1 = In all Control Modes - no matter the control place setting if communication is lost Fieldbus fault response will occur. P12.4.2.6 Modbus TCP Trusted IP Enable 1,2,3 This parameter enables the requirement that communications can only occur through trusted IP addresses found in P12.4.2.7 (cybersecurity). POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 223
Down From Keypad 1,2,3 Use this parameter to enable downloading parameter from the keypad. 0 = No 1 = All parameters 2 = All Parameter, No Motor 3 = App Parameter POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 224
3 = Calculate IGBT Temp—starting of cooling fan is based on calculated IGBT temperature. When IGBT temp = 40°C, fan starts and when temp falls down to 30°C, fan stops. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 225
Use this parameter to set the maximum scaled value when changing the display unit to a value other than the default Hz. P13.1.23 Keypad Lock Password 1,2,3 Keypad password, locks keypad with password. P13.2.1 Keypad Software Version 1,2,3 Keypad firmware Version POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 226
Total Time Power is On, Days count (resettable) P13.4.9 Trip Power Hr Count 1,2,3 Total time Power is on, Hr Count (resettable) P13.4.10 Clear Trip Power Count 1,2,3 Resets the Trip Power Counter POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 227
Digital Output status and Firmware Virtual Relay status. The Virtual RO1 and Virtual RO2 status are of internal relays in the control board not for external use, allows for turning on functions internal to the drive without the use of hardwire connections. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 228
Bit 5 = MC_Reverse Bit 13 = Motor Regulator Status not Zero Bit 6 = MC_Warning/AR-Fault Bit 14 = Ext Brake Control Bit 7 = MC_ZeroSpeed Bit 15 = Bypass Mode POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 229
PI(D) Controller 1 status indication, indicates if drive is stopped, running in PID mode, or in PID sleep mode. M6.6 PID2 Set Point PI(D) Controller 2 setpoint reference value, units will vary based on PI(D) Controller 2 units setting. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 230
Total Time Power is on, Days count (not resettable) M9.3 Total Power Hr Count 1,2,3 Total time Power is on, Hr Count (not resettable) M9.4 Trip MWh Count 1,2,3 Energy Consumption MWH Meter(resettable) POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 231
Multi-Monitor page and seeing 3 lines of Monitoring values, Up and Down keys can be used to select the row and then hitting the left arrow key will allow for editing the value then by going up and down. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Input line phase is missing Check supply voltage, fuses and cable Output Phase Superv Configurable Fault Current measurement has Check motor cable and motor detected that there is no current in one motor phase POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 233
AI1 or AI2, check cabling. External Fault Configurable Fault Digital input is activated for Check digital input settings and verify external fault input. input level, could be an external device causing fault. POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 234
OR the Check master programming to verify fieldbus control place is the remote proper addressing. control place. Bypass Overload Fault Over load when motor is in Check motor connection situation bypass mode POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 235
Drive is 10 degrees from the trip Check the drive degree Warning point of 90 deg C. Compatibility Fault Warning DSP firmware is not compatible Check the DSP firmware revision with MCB firmware POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Page 236
IO5 card firmware is not Check the IO5 card firmware revision compatible with MCB firmware Compatibility Fault Warning Profibus card firmware is not Check the Profibus card firmware revision MCU compatible with MCB firmware POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com...
Eaton is committed to minimizing the Cybersecurity risk in its products and deploys cybersecurity best practices and latest cybersecurity technologies in its products and solutions; making them more secure, reliable and competitive for our customers.
Page 238
Eaton recommends below best practices to be followed to ensure adequate cybersecurity of the setup/system • Default credentials are changed upon first login. PowerXL Series VFD should not be commissioned for production with Default credentials, it’s a serious Cybersecurity flaw as the default credentials are published...
• The latest firmware can be acquired from the www.eaton.com/drives website. There will be separate link for PowerXL Series VFD FR0 to FR6 and PowerXL Series VFD FR7 & FR8 •...
Need help?
Do you have a question about the PowerXL DH1 Series and is the answer not in the manual?
Questions and answers