Goodrive300-01A series VFD for air compressor
Power range (kW)
220–350
400–500
Terminal
sign
11–15kW
R, S, T
P1
(+)
None
(-)
None
PB
None
U, V, W
Table 3-2 Main circuit terminal description
Terminal name
7.5kW and 18.5–
110kW
Main circuit power input
None
Reserved
Reserved
Reserved
VFD output
Ground terminal for safety protection
Terminal screw
specification
M12
M12
132kW and higher
DC reactor terminal
1
DC reactor terminal
2
Reserved
None
-17-
Wiring instruction
Torque of torque driver
·
(N
m)
35
35
Terminal function
3PH
AC
input
connected to the grid
P1 and (+) connect to DC
reactor terminals
3PH AC output terminals,
connected to the motor
Each
machine
must
grounded. The grounding is
implemented through the two
PE terminals on the machine,
and the grounding resistance
is less than 10Ω.
terminals,
be