Connecting 200-240 Vac Power Cable; Ac Power Diagrams - Omron Viper 650 User Manual

Robot with ethercat
Hide thumbs Also See for Viper 650:
Table of Contents

Advertisement

2. Connect the cable shield to power supply frame ground (C).
3. Plug the mating connector end of the 24 VDC cable (F) into the 24 VDC connector on
the eCS-ECAT interface panel (A).
4. Connect the cable shield (G) to the ground point on the eCS-ECAT interface panel (A).

4.5 Connecting 200-240 VAC Power Cable

Use the following procedure to connect the 200-240 VAC cable from the power supply to the
eCS-ECAT interface panel.
Additional Information: Refer to External Connection Specifications on page 121
for more information.
IMPORTANT: Do not apply AC power until all installation steps are complete
and verified and all safety measures are in place.
WARNING: ELECTROCUTION RISK
National Electrical Code (and/or local codes) require that you provide an appro-
priately sized branch circuit protection and lockout/tagout capability. Ensure
you comply with all local and national safety and electrical codes for the
installation and operation of the robot system.
DANGER: ELECTROCUTION RISK
ISO 10218-1, Clause 5.2.4 mandates that, during installation, you must provide
a fail-safe lockout to prevent unauthorized third parties from turning on power.
WARNING: ELECTROCUTION RISK
Viper robot systems require an isolating transformer for connection to asym-
metrical mains systems or those using an isolated (impedant) neutral. Many
parts of Europe use an impedant neutral.
DANGER: ELECTROCUTION RISK
Only a skilled and instructed person must install AC power. Clause 5.2.4 of the
ISO 10218-1 requires that the person installing the system must use fail-safe
lockout measures to prevent unauthorized third parties from turning on power.
Refer to the Robot Safety Guide (Cat. No. I590) for more information.
NOTE: Install the robot system as a piece of equipment in a permanently-
installed system.

AC Power Diagrams

If using a three-phase power source, it must be symmetrically-earthed (with grounded neutral).
Connections called out as single-phase can be wired Line-to-Neutral or Line-to-Line.
76
Viper 650 and 850 Robot with EtherCAT
21861-000 Rev A