Post Installation Procedures
Note: Main Ground: 1/0 cable from the frame ground to the PANI "I" (isolated) section of the
ground window.
Note: Frame Ground: A cable #6 AWG from a frame is H-tapped into a 1/0 cable and terminates
on the "I" section of the ground window. If no ground window exists, the customer will
designate the termination point.
Note: The size of the cable is determined by the overall length of the cable run. Refer to the
Site File Book.
7. This procedure is complete.
Next, go to
How to Connect T1100 AS Chassis Ground from T1100 AS Chassis to Frame in DC
Environment
on page 88.
How to Connect T1100 AS Chassis Ground from T1100 AS Chassis to Frame in
DC Environment
In a DC environment, use this procedure for each T1100 AS unit in the heavy duty frame.
1. Remove the nuts on the T1100 AS chassis ground lugs on the back of the server (see
Chassis Ground Cable Attachment Location in DC Environment

Figure 58: Chassis Ground Cable Attachment Location in DC Environment

88
Hardware Manual
on page 88).
910-2969-001 Revision K, June 2009