Pre-Installation Site Requirements; Generic Site Requirements - Tekelec 1100 Hardware Manual

Application server
Hide thumbs Also See for 1100:
Table of Contents

Advertisement

Hardware Manual

Pre-Installation Site Requirements

Before installing any T1100 AS hardware system, ensure that the requirements described in both
of the following sections have been met.

Generic Site Requirements

#unique_55
Generic Site Requirements
Ensure that the site where the product will be installed conforms to the specifications listed in the
following sections. These specifications are standard telephony industry requirements for equipment
installation.
Fire Protection
Local fire protection codes must be satisfied in the equipment room where the system is to be
located.
Environmental Requirements
Tekelec products are designed for environments that have temperature and humidity controls.
Temperature and humidity controls must be activated as quickly as possible for equipment to
operate at an optimum level.
When temperature and humidity controls fail, the equipment has been tested to operate within
the following ranges:
Temperature
5˚ C to 40˚ C (41˚ F to 104˚ F) for normal operation
-5˚ C to 50˚ C (23˚ F to 122˚ F) for no more than 96 hours in duration and at elevations less
than 1800 meters
-5˚ C to 50˚ C (23˚ F to 122˚ F) for storing the product
Humidity
5% to 85% non-condensing for normal operation
5% to 90% non-condensing (but not to exceed 0.024 kilograms of water per kilogram of dry
air) for no more than 96 hours in duration and at elevations less than 1800 meters
Tekelec products are tested to operate at an elevations within the following range:
Minimum: 60 meters below sea level at ambient temperature of 30˚ C (86˚ F)
910-2969-001 Revision K, June 2009
on page 33
Safety and Pre-Installation Requirements
33