Post Installation Procedures
To complete the logic ground, both of the following procedures must be performed:
Attach the logic ground from the logic ground terminal block to the system bar (EF00) or to
the isolated ground of the Ground Window per this procedure.
WARNING: Be sure that there is no connection between Tekelec equipment logic
ground and the logic ground of any other telecommunications equipment.
Attach the logic ground cable from the logic ground port on the T1100 AS to the logic ground
screws on the logic ground terminal block (see
Logic Ground Terminal Strip
1. Use
How to Prepare the Cables
Note: It may be necessary to drill the central office ground window bar to accept the 3/8-inch
bolts on one-inch centers.
2. Attach one of the ground cables to the logic ground terminal strip and the other end to the
system ground bar (EF00) or the isolated ground of the ground window (see
Ground Cable Routes in DC Environment

Figure 59: Logic Ground Cable Routes in DC Environment

90
How to Connect T1100 AS Logic Ground Port to
on page 92).
on page 85 to prepare the logic ground cable (P/N 690-0131-01).
on page 90).
Hardware Manual
Figure 59: Logic
910-2969-001 Revision K, June 2009