Note: This figure shows five servers in the frame. For more complete information about the
configuration used by the application, refer to the
4. Label all cables with "TO" and "FROM" location information.
Example: FROMT1100 AS frame ground, TO isolated main ground.
5. Ensure that a bolt through any nut must show at least two threads beyond the nut, but no more
than four threads should be showing.
6. Use the lacing cord to secure a "DO NOT DISCONNECT LEAD" tag at each end of the cable,
just beyond the lug.
Apply the 145C cable tags to both ends of the frame ground cable.

Figure 57: Frame Ground Cable Attachment Locations in DC Environment

910-2969-001 Revision K, June 2009
Post Installation Procedures
Assembly
Drawing.
87