3.4 Options

See also
Connecting the auxiliary voltage (Page 72)
3.3.8.2

Auxiliary power supply 400V 3 AC 50Hz

The following components require an auxiliary power supply of 3AC 400 V:
● Fan
● Open-loop and closed-loop control
● Protection and monitoring equipment
● DC link precharging
Refer to the drive technical data for auxiliary power supply current rating. The terminal
assignment is provided in the circuit diagram of the drive.
3.3.9

Customer terminal strips

The signals are allocated to various terminal strips according to voltage level. The cables are
visually distinguished from one another by various colors. Barriers mechanically separate
cables carrying different potentials on one terminal strip. The terminals are suitable for cables
with a cross-section of 2.5 mm
The default setting and interfaces of the customer terminal strips can be found in the circuit
manual. For information about the position of the customer terminal strips within the cabinet,
see the layout diagrams.
3.4
Options
3.4.1

Auxiliary voltage supply 3 AC 200 V 50 Hz (option C30)

The auxiliary voltage of 3AC 200 V 50 Hz provided is adapted to the required auxiliary voltage
of 3AC 400 V.
See also
Auxiliary power supply 400V 3 AC 50Hz (Page 34)
3.4.2

Auxiliary voltage supply 3 AC 220 V 60 Hz (option C33)

The auxiliary voltage of 3AC 220 V 60 Hz provided is adapted to the required auxiliary voltage
of 3AC 400 V.