YASKAWA FSDrive-MV1000 Parameter Manual page 77

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

No.
Name
(Addr.)
U1-12
Drive Status
(4BH)
U1-13
Analog Input 1
(4EH)
Input Voltage
U1-14
Analog Input 2
(4FH)
Input Voltage
Output
U1-16
Frequency after
(53H)
Soft Starter
U1-17
DI-A3 Input
(58H)
Status
U1-18
oPE Fault
(61H)
Parameter
MEMOBUS/
U1-19
Modbus Error
(66H)
Code
AI-A3 Terminal
U1-21
V1 Input Voltage
(77H)
Monitor
AI-A3 Terminal
U1-22
V2 Input Voltage
(72AH)
Monitor
AI-A3 Terminal
U1-23
V3 Input Voltage
(72BH)
Monitor
U1-25
Software
(4DH)
Number (Flash)
U1-26
Software No.
(5BH)
(ROM)
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
All Modes
Verifies the drive operation status.
U1 - 12=
0 0 0 0 0 0 0 0
All Modes
Displays the voltage of analog input 1.
All Modes
Displays the input voltage of analog input 2.
All Modes
Displays output frequency with ramp time and S-curves. Units determined
by o1-03.
All Modes
Displays the reference value input from the DI-A3 option card.
Display will appear in hexadecimal as determined by the digital card input
selection in F3-01.
3FFFF: Set (1 bit) + sign (1 bit) + 16 bits
All Modes
Displays the parameter number that caused the oPE
write error) error.
All Modes
Displays the contents of a MEMOBUS/Modbus error.
U1 - 19=
0 0 0 0 0 0 0 0
All Modes
Displays the input voltage to terminal V1 on analog input card AI-A3.
All Modes
Displays the input voltage to terminal V2 on analog input card AI-A3.
All Modes
Displays the input voltage to terminal V3 on analog input card AI-A3.
All Modes
Displays FLASH ID.
All Modes
Displays ROM ID.
Description
1: ON
0: OFF
During run
During zero-speed
During REV
During fault reset
signal input
During speed agree
During ready
During alarm detection
During fault detection
or Err (EEPROM
1: ON
0: OFF
CRC Error
Data Length Error
Not used
(always OFF)
Parity Error
Overrun Error
Framing error
Time Out
Not used
(always OFF)
1.3 Parameter Table
Analog Output
Level
common_
No signal output
available
common_
10 V: 100%
common_
10 V: 100%
common_
10 V: Max
frequency
common_
No signal output
available
common_
No signal output
available
common_
No signal output
available
common_
10 V: 100%
common_
10 V: 100%
common_
10 V: 100%
No signal output
common_
available
No signal output
common_
available
Unit
Page
0.1%
0.1%
0.01 Hz
0.1%
0.1%
0.1%
77

Advertisement

Table of Contents
loading