L4-06: Frequency Reference at Reference Loss
n
Sets the frequency reference level at which the drive runs when L4-05 = 1 and a reference loss was detected. The value is
set as a percentage of the frequency reference when the loss was detected.
No.
L4-06
Frequency Reference at Reference Loss
L4-07: Speed Agreement Detection Selection
n
Determines when frequency detection is active using parameters L4-01 through L4-04.
No.
L4-07
Speed Agreement Detection Selection
Setting 0: Detection during run (no detection when drive output shut down)
Setting 1: Detection always enabled
u L5: Fault Restart
After a fault has occurred, this function attempts to automatically restart the motor and continue operation instead of
stopping.
The drive can be set up to perform a self-diagnostic check and resume the operation after a fault has occurred. If the
self-check is successful and the cause of the fault has disappeared, the drive restarts by first performing Speed Search
(Refer to
b3: Speed Search on page 110
Note: 1. The wiring sequence should remove the Forward/Reverse command when a fault is triggered and output is shut off.
2. With the Forward/Reverse command removed, the drive can perform a self-diagnostic check and attempt to reset the fault
automatically.
The drive can attempt to restart itself following the faults listed below.
Fault
CF
Control Fault
CFA nn CoF
Current Offset Fault
CFA nn FU
Fuse Blowout
CFA nn OC
Overcurrent
CFA nn oH1
IGBT Overheating 1
CFA nn OV1
Overvoltage 1
CFA nn OV2
Overvoltage 2
GF
Ground Fault
LF
Output Open Phase
<1> When L2-01 is set to 1 or 2 (continue operation during momentary power loss ride-thru)
Use parameters L5-01 to L5-05 to set up automatic fault restart.
To output a signal during fault restart, set H2-01, H2-02, or H2-03 to 1E.
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Name
Name
for details).
Name
Setting Range
0.0 to 100.0%
Setting Range
0 or 1
Fault
LIN nn
Link Fault Communication Fault
oH
IGBT Overheating
oL1
Motor Overload
oL2
Drive Overload
oL3
Overtorque 1
oL4
Overtorque 2
Uv1
DC Bus Undervoltage
VUB
Output Voltage Unbalance
2.8 L: Protection Functions
Default
80.0%
Default
0
Name
<1>
211