YASKAWA FSDrive-MV1000 Parameter Manual page 97

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

10
The display automatically returns to the display shown in step 6.
Table 2.3 Check to see if A1-02 is locked (continuing from step 10 above)
1
Press
to display A1-02.
2
Press
, making sure that the settings cannot be changed.
3
Press
to return to the first display.
Table 2.4 Enter the Password to Unlock Parameters (continuing from step 2 above)
1
Scroll to the right by pressing
2
Select the flashing digits by pressing
3
Press
to display A1-04, then press
4
Press
or
5
Press
to save what was entered.
6
The drive returns to the parameter display.
7
Press
to display A1-02.
Press
to display the value set in A1-02. If the first "0" blinks, the parameter settings are
8
unlocked.
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Step
Step
Step
.
.
.
to enter the password.
2.1 A: Initialization
Display/Result
-PRMSET-
PRG
Select Password
A1-
05
= 1234
(0~9999)
"0"
FWD
Display/Result
-PRMSET-
PRG
Control Method
A1-02= 2
∗2∗
Open Loop Vector
FWD
"02" flashes
- MODE -
PRG
Programming
HELP
FWD
DATA
Display/Result
-PRMSET-
PRG
Initialization
A1-00=
0
Select Language
FWD
-PRMSET-
PRG
Select Language
A1-00=
0
∗0∗
English
FWD
"00" flashes
-PRMSET-
PRG
Enter Password
A1-
04
=
0
(0~9999)
"0"
FWD
-PRMSET-
PRG
Enter Password
A1- 04 =
1234
(0~9999)
"0"
FWD
Entry Accepted
-PRMSET-
PRG
Enter Password
A1-
04
=
0
(0~9999)
"0"
FWD
-PRMSET-
PRG
Control Method
A1-02= 2
∗2∗
Open Loop Vector
FWD
-PRMSET-
PRG
Control Method
A1-02=
2
∗2∗
Open Loop Vector
FWD
97