YASKAWA FSDrive-MV1000 Parameter Manual page 107

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

b1-07: LOCAL/REMOTE Run Selection
n
The drive has three separate control sources that can be switched using contact inputs (H1-
Selection) or 2 (External reference 1/2)) or the LO/RE key on the digital operator.
Selection on page
172,
Setting 2: External Reference 1/2 Selection on page 172
REMOTE) Key Function Selection on page 233
• LOCAL: Digital operator. The digital operator is used to set the frequency reference and Run command.
• REMOTE: External reference 1. The frequency reference and Run command source are set by b1-01 and b1-02.
• REMOTE: External reference 2. The frequency reference and Run command source are set by b1-15 and b1-16.
When switching from LOCAL to REMOTE, or between External reference 1 and External reference 2, the Run
command may already be present at the location to which the source was switched. In this case, use parameter b1-07 to
determine how the Run command is treated.
No.
b1-07
Setting 0: Run command must be cycled
When the Run command source differs between the old and new source (e.g., the old source was the terminals and the
new source is serial communication), and the Run command is active at the new source as the switch over occurs, the
drive will not start or will stop operation if it was previously running. The Run command must be cycled at the new
source to restart the drive.
Setting 1: Accept Run command at the new source
When the Run command is active at the new source, the drive starts or continues operation if it was previously running.
WARNING! The drive may start unexpectedly if switching control sources when b1-07 = 1. Clear all personnel away from rotating
machinery and electrical connections prior to switching control sources. Failure to comply may cause death or serious
injury.
b1-08: Run command selection while in Programming Mode
n
As a safety precaution, the drive will not normally respond to a Run command input when the digital operator is being
used to adjust parameters in the Programming Mode (Verify Menu, Setup Mode, Parameter Settings Mode, and
Auto-Tuning Mode).
No.
b1-08
Setting 0: Disabled
A Run command is not accepted while the digital operator is in the Programming Mode.
Setting 1: Enabled
A Run command is accepted in any digital operator mode.
Setting 2: Prohibit programming during run
It is not possible to enter the Programming Mode as long as the drive output is active. The Programming Mode cannot be
displayed during Run.
b1-15: Frequency Reference Selection 2
n
Refer to b1-01: Frequency Reference Selection 1 on page 101
No.
b1-15
b1-16: Run Command Selection 2
n
Refer to b1-02: Run Command Selection 1 on page 102
No.
b1-16
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Name
LOCAL/REMOTE Run Selection
Name
Run Command Selection while in Programming Mode
Name
Frequency Reference Selection 2
Name
Run Command Selection 2
for details.
for details.
0 to 3
for details.
0 to 3
2.2 b: Application
= 1 (LOCAL/REMOTE
Refer to Setting 1: LOCAL/REMOTE
and
Refer to o2-01: LO/RE (LOCAL/
Setting Range
0 or 1
Setting Range
0 to 2
Setting Range
0
Setting Range
0
Default
0
Default
0
Default
Default
107

Advertisement

Table of Contents
loading

Table of Contents