YASKAWA FSDrive-MV1000 Parameter Manual page 54

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

1.3 Parameter Table
H1-
Function
Setting
71
Speed/Torque Control Switch
73
Door Switch NC
75
Up 2 Command
76
Down 2 Command
77
ASR Gain Switch
External Torque Reference
78
Polarity Inversion
Synchronous Transfer
80
Command from Drive to
Commercial Power Supply
Synchronous Transfer
81
Command from Commercial
Power Supply to Drive
Close Signal for Commercial
82
Power Supply Side Breaker
Close Signal for Drive
83
Secondary Side Breaker
No.
Name
(Addr.)
H2-01
Contact Output 1
(40BH)
Function Selection
H2-02
Contact Output 2
(40CH)
Function Selection
54
H1 Contact Input Selections
V/f
Open: Speed Control
Closed: Torque Control
All Modes
Closed: The drive panel door is closed. The dO fault occurs if the door is opened while
the main power supply is turned on.
Note: 1. This setting is available from the drive software versions S0108 and later.
2. Make sure to input the door switch signal to the contact inputs.
All Modes
Used to control the bias added to the frequency reference by the Up/Down 2 function.
The Up 2 and Down 2 commands must always be used in conjunction with one another.
V/f
Open: ASR proportional gain 1 (C5-01)
Closed: ASR proportional gain 2 (C5-03)
V/f
Open: Forward torque reference
Closed: Reverse polarity
All Modes
Closed: Synchronous Transfer from the drive to a commercial power supply is enabled.
Note: This function cannot be used simultaneously with settings 80 and 81. If
switching between settings 80 and 81, set the active one to be disabled before
setting the other one to be enabled.
All Modes
Closed: Synchronous Transfer from a commercial power supply to the drive is enabled.
Note: This function cannot be used simultaneously with settings 80 and 81. If
switching between settings 80 and 81, set the active one to be disabled before
setting the other one to be enabled.
All Modes
Open: The commercial power supply side breaker is open.
Closed: The commercial power supply side breaker is closed.
Note: 1. Use this setting if the Synchronous Transfer is used.
2. Make sure the contact input terminal set to 82 closes as an answer signal when
the commercial power supply side breaker is closed and opens when the
commercial power supply side breaker is open.
All Modes
Open: The drive secondary side breaker is open.
Closed: The drive secondary side breaker is closed.
Note: 1. Use this setting if the Synchronous Transfer is used.
2. Make sure the contact input terminal set to 82 closes as an answer signal when
the commercial power supply side breaker is closed and opens when the
commercial power supply side breaker is open.
H2: Contact Outputs
All Modes
Refer to
H2 Contact Output Settings on page 56
values.
All Modes
Refer to
H2 Contact Output Settings on page 56
values.
Description
OLV
CLV
OLV
CLV
CLV
OLV
Description
for a description of setting
for a description of setting
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
common
common
common_
common
common
common
common
common
common
Setting
common_
Default: 10E
Min: 0
Max: 1FF
Default: E
common_
Min: 0
Max: 1FF
Reference
Page
179
179
179
180
180
181
181
181
181
Page
<45>
181
181

Advertisement

Table of Contents
loading

Table of Contents