YASKAWA FSDrive-MV1000 Parameter Manual page 33

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

No.
Name
(Addr.)
C3-01
Slip Compensation
(20FH)
Gain
C3-02
Slip Compensation
(210H)
Primary Delay Time Adjusts the slip compensation function delay time used for motor 1.
C3-03
Slip Compensation
(211H)
Limit
Slip Compensation
C3-04
Selection during
(212H)
Regeneration
Output Voltage
C3-05
Limit Operation
(213H)
Selection
Output Voltage
Limit Operation
C3-16
Start Level
(261H)
(Percentage
Modulation)
C3-17
Maximum Output
Voltage Limit Level Sets the output voltage limit operation determined by C3-18 (percentage
(262H)
C3-18
Output Voltage
(263H)
Limit Level
C3-21
Motor 2 Slip
(33EH)
Compensation Gain Sets the slip compensation gain used for motor 2.
C3-22
Motor 2 Slip
(241H)
Compensation
Primary Delay Time Sets the slip compensation delay time used for motor 2.
C3-23
Motor 2 Slip
Compensation Limit Sets the upper limit for the slip compensation function for motor 2. Set as a
(242H)
Motor 2 Slip
C3-24
Compensation
(243H)
Selection During
Regeneration
C4-01
Torque
(215H)
Compensation Gain Sets the gain for the automatic torque (voltage) boost function and helps to
Torque
C4-02
Compensation
(216H)
Primary Delay Time
1
Torque
C4-03
Compensation at
(217H)
Forward Start
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
C3: Slip Compensation
All Modes
Sets the gain for the motor slip compensation function used for motor 1.
V/f
OLV
V/f
OLV
Sets an upper limit for the slip compensation function as a percentage of
motor rated slip for motor 1 (E2-02).
V/f
OLV
0: Disabled
1: Enabled above 6 Hz.
2: Enabled whenever slip compensation is possible.
V/f
OLV
0: Disabled
1: Enabled. Automatically decreases motor flux when output voltage
saturation is reached.
V/f
OLV
Sets the output voltage limit operation start level (percentage modulation)
when C3-05 is enabled.
V/f
OLV
modulation) when C3-05 is enabled.
V/f
OLV
Sets the maximum percentage of output voltage reduction when parameter
C3-05 is enabled.
All Modes
V/f
OLV
V/f
OLV
percentage of the motor rated slip (E4-02).
V/f
OLV
0: Disabled
1: Enabled above 6 Hz.
2: Enabled whenever slip compensation is possible.
C4: Torque Compensation
V/f
OLV
produce better starting torque. Used for motor 1.
V/f
OLV
Sets the torque compensation filter time.
V/f
OLV
Sets torque compensation at forward start as a percentage of motor torque.
Description
CLV
CLV
CLV
CLV
common
CLV
CLV
CLV
common_
CLV
common
CLV
CLV
common
CLV
CLV
common
CLV
common
1.3 Parameter Table
Setting
Default:
<10>
common_
Min: 0.0
Max: 2.5
Default:
<10>
Min: 0 ms
common
Max: 10000 ms
Default: 200%
common
Min: 0%
Max: 250%
Default: 0
common
Min: 0
Max: 2
Default:
<10>
Min: 0
Max: 1
Default: 85.0%
common
Min: 70.0%
Max. 90.0%
Default: 90.0%
common
Min: 85.0%
Max: 100.0%
Default: 90.0%
common
Min: 30.0%
Max: 100.0%
Default:
<15>
Min: 0.0
Max: 2.5
Default:
<15>
Min: 0 ms
Max: 10000 ms
Default: 200%
common
Min: 0%
Max: 250%
Default: 0
Min: 0
Max: 2
Default:
<10>
common
Min: 0.00
Max: 2.50
Default:
<10>
Min: 0 ms
Max: 60000 ms
Default: 0.0%
Min: 0.0%
Max: 200.0%
Page
131
131
131
132
132
132
133
133
133
133
133
134
134
135
135
33