YASKAWA FSDrive-MV1000 Parameter Manual page 204

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

2.8 L: Protection Functions
KEB Operation Wiring Example
n
Figure 2.72
shows a wiring example for triggering the KEB Ride-Thru at power loss using an undervoltage relay. If
power loss occurs, the undervoltage relay triggers KEB Ride-Thru at contact input 9. Note that an additional dynamic
braking option is required if System KEB Ride-Thru 1 is used.
Note: Make sure the Run command is not switched off during momentary power loss ride-thru. If the Run command is shut off, the
drive will not accelerate back to speed when the power is restored.
Figure 2.72
Note: When a momentary power loss ride-thru occurs, check if the Run command remains in effect. If the Run command is turned
OFF, the drive will not be able to accelerate to the speed set in the frequency reference when the power is restored.
L2-02: Momentary Power Loss Ride-Thru Time
n
Sets the maximum time allowed to ride through a power loss ride-thru. If power loss ride-thru operation exceeds this
time, the drive will attempt to accelerate back to frequency reference. This parameter is valid if L2-01 = 1.
Note: The amount of time the drive is capable of recovering after a power loss is determined by the capacity of the drive. Drive
capacity determines the upper limit for L2-02.
No.
L2-02
Momentary Power Loss Ride-Thru Time
<1> For details on the default settings, refer to
L2-03: Momentary Power Loss Ride-Thru Minimum Baseblock Time
n
Sets the minimum baseblock time when power is restored following a momentary power loss Ride-Thru. This determines
the time the drive waits for the residual voltage in the motor to dissipate. Increase this setting if overcurrent or
overvoltage occurs at the beginning of Speed Search, after a power loss ride-thru, or during DC Injection Braking.
No.
Momentary Power Loss Ride-Thru Minimum Baseblock
L2-03
<1> For details on the default settings, refer to
L2-04: Momentary Power Loss Ride-Thru Voltage Recovery Ramp Time
n
Sets the time for the drive to restore the output voltage to the level specified by the V/f pattern after Speed Search. The
setting value determines the time for the voltage to go from 0 V to the maximum voltage.
No.
Momentary Power Loss Ride-Thru Voltage Recovery
L2-04
<1> For details on the default settings, refer to
204
R
L1
S
L2
T
L3
UV Detection
Relay
9 - KEB Command 1
10
13 - Run command
14
Figure 2.72 Example Wiring for KEB Ride-Thru Function
Name
Defaults by Drive Model Selection (o2-04) on page
Name
Time
Defaults by Drive Model Selection (o2-04) on page
Name
Ramp Time
Defaults by Drive Model Selection (o2-04) on page
U
V
W
Setting Range
0.0 to 25.5 s
87.
Setting Range
0.1 to 20.0 s
87.
Setting Range
0.0 to 10.0 s
87.
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
M
Default
Determined by o2-04
<1>
Default
Determined by o2-04
<1>
Default
Determined by o2-04
<1>