u F6 and F7: Communication Option Card Settings
These parameters configure communication option cards and set the fault detection methods.
Some parameters apply to all communication option cards and some parameters apply to certain network options only.
The option cards are applicable to the parameter rows marked with an "O".
Parameter
F6-01 to F6-03
F6-04
F6-06 to F6-08
F6-30 to F6-32
F6-50 to F6-63
F7-01 to F7-15
F7-16
F7-17 to F7-42
F6-01: Communications Error Operation Selection
n
Determines drive operation when a communication error occurs.
No.
F6-01
Setting 0: Ramp to stop (uses the deceleration time set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop time set to C1-09)
Setting 3: Alarm only (continue operation)
F6-02: External Fault from Comm. Option Detection Selection
n
Determines the detection method of an external fault initiated by a communication option (EF0).
No.
F6-02
External Fault from Comm. Option Detection Selection
Setting 0: Always detected
Setting 1: Detection during run only
F6-03: External Fault from Comm. Option Operation Selection
n
Determines the operation when an external fault is initiated by a communication option (EF0).
No.
F6-03
External Fault from Comm. Option Operation Selection
Setting 0: Ramp to stop
Setting 1: Coast to stop
Setting 2: Fast Stop
Setting 3: Alarm only (continue operation)
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
PROFIBUS-DP
Parameter Name
Communications Error Operation Selection
Parameter Name
Parameter Name
Communication Protocol
DeviceNet
Setting Range
0 to 3
Setting Range
0 or 1
Setting Range
0 to 3
2.6 F: Option Settings
Modbus TCP/IP
Default
1
Default
0
Default
1
169