YASKAWA FSDrive-MV1000 Parameter Manual page 185

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

Setting 5: Frequency Detection 2
Output closes when the output frequency or motor speed (CLV) is above the detection level set in L4-01. The terminal
remains closed until the output frequency or motor speed falls below L4-01 minus the setting of L4-02.
Status
Open
Output frequency or motor speed is below L4-01 minus L4-02 or has not exceeded L4-01.
Closed
Output frequency or motor speed exceeded L4-01.
Note: Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.
Figure 2.56
Frequency
Detection 2
Refer to
L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 210
Setting 6: Drive Ready
Output closes when the drive is ready to operate the motor. The terminal will not close under the conditions listed below,
and any Run commands will be disregarded.
• When the power is shut off
• During a fault
• When the internal power supply of the drive has malfunctioned
• When a parameter setting error makes it impossible to run
• Although stopped, an overvoltage or undervoltage situation occurs
• While editing a parameter in the Programming Mode (when b1-08 = 0)
Setting 7: DC Bus Undervoltage
Output closes when the DC bus voltage or control circuit power supply drops below the trip level set in L2-05. A fault in
the DC bus circuit will also cause the terminal to set for "DC bus undervoltage" to close.
Status
Open
DC bus voltage is above the level set in L2-05.
Closed
DC bus voltage has fallen below the trip level set in L2-05.
Setting 8: During Baseblock (N.O.)
Output closes to indicate that the drive is in a baseblock state. While in baseblock, output transistors do not switch and no
main circuit voltage is output.
Status
Open
Drive is not in a baseblock state.
Closed
Baseblock is being executed.
Setting 9: Frequency Reference Source
A contact output programmed for this function shows the frequency reference source that is currently selected.
Status
Open
Frequency reference is provided from External reference 1 (b1-01) or External reference 2 (b1-15).
Closed
Frequency reference is being sourced from the digital operator.
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Output Frequency
or Motor Speed
OFF
(open)
ON (closed)
Figure 2.56 Frequency Detection 2 Time Chart
Description
common_TMonly
L4-02
L4-01
Description
Description
Description
2.7 H: Terminal Functions
L4-01
L4-02
for more details.
185