C3-17: Maximum Output Voltage Limit Level (Percentage Modulation)
n
Sets the output voltage limit operation determined by C3-18 (percentage modulation) when C3-05 is enabled.
No.
Maximum Output Voltage Limit Level (Percentage
C3-17
C3-18: Output Voltage Limit Level
n
Sets the maximum percentage of output voltage reduction when C3-05 is enabled.
No.
C3-18
C3-21: Motor 2 Slip Compensation Gain
n
Improves speed accuracy for motor 2 and functions in the same way that C3-01 functions for motor 1. Adjust this
parameter only after setting the motor rated current (E4-01), motor rated slip (E4-02), and the motor no-load current
(E4-03).
Adjustments might be needed in the following circumstances:
• Increase C3-21 if the motor at constant speed is slower than the frequency reference.
• Decrease C3-21 if the motor at constant speed is faster than the frequency reference.
No.
C3-21
Motor 2 Slip Compensation Gain
<1>
Refer to E3-01 (Motor 2 Control Mode) Dependent Parameters on page 86
C3-22: Motor 2 Slip Compensation Primary Delay Time
n
Functions for motor 2 in the same way that C3-02 functions for motor
Delay Time on page 131
No.
Motor 2 Slip Compensation Primary Delay Time
C3-22
<1> Refer to
E3-01 (Motor 2 Control Mode) Dependent Parameters on page 86
C3-23: Motor 2 Slip Compensation Limit
n
Sets the upper limit for the slip compensation function as a percentage of the motor rated slip (E4-02).
No.
C3-23
Motor 2 Slip Compensation Limit
The slip compensation limit is constant throughout the constant torque range (frequency reference
constant power range (frequency reference > E3-06), it is increased based on C3-23 and the output frequency as
illustrated in
Figure
2.26.
Figure 2.26
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Name
Modulation)
Name
Output Voltage Limit Level
Name
for details on adjusting this parameter.
Name
Constant
Name
E3-04
E3-06 × C3-23
C3-23
Figure 2.26 Slip Compensation Limit
Setting Range
85.0 to 100.0%
Setting Range
30.0 to 100.0%
Setting Range
0.0 to 2.5
for details on default settings.
1.Refer to C3-02: Slip Compensation Primary
Setting Range
0 to 10000 ms
for details on default settings.
Setting Range
0 to 250%
Output Frequency
E3-06
E3-04
Base
Maximum
Frequency
Frequency
Default
Determined by E3-01
Default
Determined by E3-01
Default
200%
E3-06). In the
common_TMonly
2.3 C: Tuning
Default
90.0%
Default
90.0%
<1>
<1>
133