2.10 o: Operator Related Settings
o2-01
b1-07
0
1
o2-02: STOP Key Function Selection
n
Determines if the STOP key on the digital operator can still be used to stop drive operation when the drive is being
controlled from a remote source (i.e., not from digital operator).
No.
o2-02
STOP Key Function Selection
Setting 0: Disabled
Setting 1: Enabled
The STOP key can be used to terminate drive operation, even if the Run command source is not assigned to the digital
operator. If the drive is stopped by pressing the STOP key, the Run command must be re-input to restart the drive.
o2-03: User Parameter Default Value
n
After drive parameters are set up completely, the values set can be saved as user-set default values using parameter
o2-03. Once this has been done, the "Initialize Parameters" parameter (A1-03) will offer the choice of "1110: User
Initialize". Choosing A1-03 = "1110: User Initialize" will reset all parameters to the values saved as user-set defaults.
Refer to
A1-03: Initialize Parameters on page 95
No.
o2-03
User Parameter Default Value
Setting 0: No change (awaiting command)
Setting 1: Set User Initialize values
The current parameter settings are saved as user-set default for User Initialize. After o2-03 is set to 1 and the ENTER key
is pressed, the values are saved and the display returns to 0.
Setting 2: Clear User Initialize Values
All user-set defaults for "User Initialize" are cleared. After o2-03 is set to 2 and the ENTER key is pressed, the values are
erased and the display returns to 0.
o2-04: Drive Capacity Selection
n
Set this parameter when replacing the controller. For information on the drive model selection, refer to
Model Selection (o2-04) on page
NOTICE: Drive performance will suffer if the correct drive capacity is not set for o2-04, and protective functions will fail to operate
properly.
No.
o2-04
Drive Capacity Selection
Note: Change settings only when necessary.
o2-05: Frequency Reference Setting Method Selection
n
Determines whether the ENTER key must be pressed after changing the frequency reference using the digital operator
while in the Drive Mode.
No.
Frequency Reference Setting Method
o2-05
234
Table 2.30 LO/RE Key and b1-07
Switch from LOCAL to REMOTE
0
Not possible
1
Not possible
0
Will not run until a new Run command is entered. Run not possible
If a Run command is entered, the drive will start
1
running as soon as the LO/RE key is pushed to
change from LOCAL to REMOTE.
Name
Name
87.
Name
Name
Selection
Setting Range
0 or 1
for details on drive initialization.
Setting Range
0 to 2
Setting Range
Setting Range
0, 1
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Switch from REMOTE to LOCAL
Not possible
Not possible
Run not possible
1
0
Defaults by Drive
Determined by drive capacity
0
Default
Default
Default
Default