YASKAWA FSDrive-MV1000 Parameter Manual page 91

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

Table 1.7 6 kV Class Drives Default Settings by Drive Model Selection
No.
Name
<61>
Model
CIMR-MV2
Drive Model
o2-04
Selection
E2-11 (E4-11)
Motor Rated Power kW
V/f Gain during Speed
b3-04
Search
Output Current 1 during
b3-06
Speed Search
Speed Search Method
Switching Level (Speed
b3-11
Estimate Type Speed
Search)
E2-01 (E4-01) Motor Rated Current
E2-02 (E4-02) Motor Rated Slip
E2-03 (E4-03) Motor No-Load Current
Motor Line-to-Line
E2-05 (E4-05)
Resistance
Motor Leakage
E2-06 (E4-06)
Inductance
Motor Iron Loss for
E2-10 (E4-10)
Torque Compensation
Momentary Power Loss
L2-02
Ride-Thru Time
Momentary Power Loss
L2-03
Ride-Thru Minimum
Baseblock Time
Momentary Power Loss
L2-04
Ride-Thru Voltage
Recovery Time
Undervoltage Detection
L2-05
Level (Uv)
L8-02
Overheat Alarm Level
<62>
Output Ground Fault
L8-09
Detection Selection
FAN Board Use
L8-33
Selection
Transformer Overheat
L8-87
Alarm (TMA) Level
Transformer Overheat
L8-88
Fault (TME) Level
Hunting Prevention
n1-03
Time Constant
Output Current
n9-02
Detection Gain
Input Current
n9-71
Conversion Coefficient
Reference Voltage for
o2-11
Input Voltage Detection
<61> Parameter numbers shown in parenthesis are valid for motor 2.
<62> The alarm detection level differs for each drive model because of the different thermistor position on each drive.
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Unit
035
050
070
60
61
62
320
460
640
%
80
80
80
0.5
0.5
0.5
%
5.0
5.0
5.0
A
30.0
45.0
60.0
Hz
0.25
0.25
0.25
A
8.0
11.0
15.0
W
0.300
0.300
0.300
%
20.0
20.0
20.0
W
0
0
0
s
2.0
2.0
2.0
s
2.0
2.0
2.0
s
5.0
5.0
5.0
V
1188
1188
1188
105
105
105
1
1
1
2
2
2
°C
130
130
130
°C
140
140
140
ms
30
30
30
1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000
0.0340 0.0340 0.0235 0.0150 0.0110 0.0094 0.0060 0.0060 0.0040 0.0040 0.0030
V
6600
6600
6600
1.5 Defaults by Drive Model Selection (o2-04)
Default Settings
100
140
200
260
63
64
65
66
910
1280
1830
2380
80
80
80
80
0.5
0.5
0.5
0.5
5.0
5.0
5.0
5.0
85.0
120.0
170.0
220.0
0.25
0.25
0.25
0.25
21.0
30.0
43.0
55.0
0.300
0.300
0.300
0.300
20.0
20.0
20.0
20.0
0
0
0
0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
5.0
5.0
5.0
5.0
1188
1188
1188
1188
105
105
105
95
1
1
1
1
2
2
2
2
130
130
130
130
140
140
140
140
30
30
30
30
6600
6600
6600
6600
330
400
520
650
67
68
69
6A
3020
3660
4760
5940
80
80
80
80
0.5
0.5
0.5
0.5
5.0
5.0
5.0
5.0
280.0
340.0
440.0
550.0
0.25
0.25
0.25
0.25
70.0
85.0
110.0
138.0
0.300
0.300
0.300
0.300
20.0
20.0
20.0
20.0
0
0
0
0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
5.0
5.0
5.0
5.0
1188
1188
1188
1188
105
105
100
105
1
1
1
1
2
2
2
2
130
130
130
130
140
140
140
140
30
30
30
30
6600
6600
6600
6600
91

Advertisement

Table of Contents
loading

Table of Contents