YASKAWA FSDrive-MV1000 Parameter Manual page 48

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

1.3 Parameter Table
No.
Name
(Addr.)
F7-13
Address Mode at
(3F1)
Startup
F7-14
Duplex Mode
(3F2)
Selection
F7-15
Communication
(3F3)
Speed Selection
<50>
F7-16
Communication
(3F4)
Loss Time-out
F7-17
EtherNet/IP Speed
(3F5)
Scaling Factor
F7-18
EtherNet/IP Current
(3F6)
Scaling Factor
F7-19
EtherNet/IP Torque
(3F7)
Scaling Factor
F7-20
EtherNet/IP Power
(3F8)
Scaling Factor
F7-21
EtherNet/IP Voltage
(3F9)
Scaling Factor
F7-22
EtherNet/IP Time
(3FA)
Scaling
F7-23 to
Dynamic Output
F7-32
Assembly
(3FB to
Parameters
404)
F7-33 to
Dynamic Input
F7-42
Assembly
(405 to
Parameters
40E)
<3> Parameter setting value is not reset to the default value when the drive is initialized (A1-03 = 1110/2220).
<10> Default setting is determined by A1-02, Control Method Selection.
<47> Cycle power for setting changes to take effect.
<48> If F7-13 is set to 0, then all IP Addresses (as defined with parameters F7-01 to F7-04) must be unique.
<49> Set F7-01 to F7-12 when F7-13 is set to 0.
<50> Set F7-15 when F7-14 is set to 0 or 2.
48
All Modes
Selects how the option address is set.
0: Static
<48>
1: BOOTP
2: DHCP
All Modes
Selects duplex mode setting.
0: Half duplex forced
1: Auto-negotiate duplex mode and communication speed
2: Full duplex forced
All Modes
Sets the communication speed.
10: 10 Mbps
100: 100 Mbps
All Modes
Sets the time-out value for communication loss detection in tenths of a
second. A value of 0 disables the connection time-out.
Example: An entered value of 100 represents 10.0 seconds.
All Modes
Sets the scaling factor for the speed monitor in EtherNet/IP Class ID 2AH
Object.
All Modes
Sets the scaling factor for the output current monitor in EtherNet/IP Class ID
2AH Object.
All Modes
Sets the scaling factor for the torque monitor in EtherNet/IP Class ID 2AH
Object.
All Modes
Sets the scaling factor for the power monitor in EtherNet/IP Class ID 2AH
Object.
All Modes
Sets the scaling factor for the voltage monitor in EtherNet/IP Class ID 2AH
Object.
All Modes
Sets the scaling factor for the time monitor in EtherNet/IP Class ID 2AH
Object.
All Modes
Parameters used in Output Assembly 116. Each parameter contains a
MEMOBUS/Modbus address. The value received for Output Assembly 116
will be written to this corresponding MEMOBUS/Modbus address. A
MEMOBUS/Modbus address value of 0 means that the value received for
Output Assembly 116 will not be written to any MEMOBUS/Modbus
register.
All Modes
Parameters used in Input Assembly 166. Each parameter contains a
MEMOBUS/Modbus address. The value sent for Input Assembly 166 will
be read from this corresponding MEMOBUS/Modbus address. A
MEMOBUS/Modbus address value of 0 means that the value sent for Input
Assembly 166 is not defined by the user, therefore the option default register
value will be returned.
Refer to EtherNet/IP Technical Manual for definitions of the default
MEMOBUS/Modbus registers.
Description
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Setting
common_
TMonly
Default: 2
Min: 0
Max: 2
common_
TMonly
Default: 1
Min: 0
Max: 2
common_
Default: 10
TMonly
Min: 10
Max: 100
common_
Default: 0
TMonly
Min: 0
Max: 300
Default: 0
common_
TMonly
Min: -15
Max: 15
Default: 0
common_
TMonly
Min: -15
Max: 15
Default: 0
common_
TMonly
Min: -15
Max: 15
Default: 0
common_
TMonly
Min: -15
Max: 15
Default: 0
common_
TMonly
Min: -15
Max: 15
Default: 0
common_
TMonly
Min: -15
Max: 15
common_
TMonly
Default: 0
common_
TMonly
Default: 0