u n7: Synchronous Transfer with a Commercial Power Supply (Available from the
Drive Software Versions S0103 and Later.)
The Synchronous Transfer cannot be used when A1-02 is set to 2 (Open Loop Vector Control).
System Configuration
n
Figure 2.81
shows the system configuration for Synchronous Transfer.
To perform a Synchronous Transfer, the following devices and interface must be connected in addition to the standard
connections for the drive.
External sequence circuits for Synchronous Transfer are also required.
• Inside drive
• Drive/external sequence circuits
• Drive/motor
• Commercial power supply/motor
• Drive/breaker
<1> The breaker command requires a separate relay that satisfies the specifications of the breaker to be used.
Figure 2.81
Synchronous Transfer
Command from Commercial
Power Supply to Drive(DI)
Commercial
Power Supply
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
:
Input voltage detection circuit, contact circuits (DI and DO)
:
Synchronous Transfer command from drive to commercial power supply (DI), Synchronous Transfer
command from commercial power supply to drive (DI), completion signal for Synchronous Transfer
(DO)
:
Reactor, drive secondary side breaker
:
Commercial power supply side breaker, commercial power supply current detector (phase R and T)
:
Close command for drive secondary side breaker (DO), close signal for drive secondary side breaker
(DI), close command for commercial power supply side breaker (DO), close signal for commercial
power supply side breaker (DI)
Synchronous Transfer Command
Synchronous Transfer Command
from Drive to Commercial Power Supply (DI)
Completion Signal for
Synchronous Transfer
Drive
Close Command (DO)
Commercial
Power Supply
Close Signal (DI)
Current Detector
Figure 2.81 Synchronous Transfer System Configuration
External Command
Transfer Device
Reactor
Close Command (DO)
Close Signal (DI)
Commercial power
supply side breaker
2.9 n: Special Adjustments
, external terminals for interface
<1>
Drive secondary
side breaker
M
Motor
225