YASKAWA FSDrive-MV1000 Parameter Manual page 168

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

2.6 F: Option Settings
F4-15: Analog Output 6 (Terminal V2) Signal Level Selection
n
Sets the signal level for analog output 6 (terminal V2).
No.
F4-15
Setting 0: 0 to 10 Vdc
Setting 1: -10 to 10 Vdc
Using Gain and Bias to Adjust Output Signal Level
The output signal is adjustable while the drive is stopped.
Analog Output 5 (Terminal V1)
1. View the value set to F4-02 (Analog Output 5 (Terminal V1) Gain) on the digital operator. A voltage equal to 100% of
the parameter being set in F4-01 will be output from analog output 5 (terminal V1).
2. Adjust F4-02 viewing the monitor connected to the analog output 5 (terminal V1).
3. View the value set to F4-03 on the digital operator, analog output 5 (terminal V1) will output a voltage equal to 0% of
the parameter being set in F4-01.
4. Adjust F4-03 viewing the output signal on the analog output 5 (terminal V1).
Analog Output 6 (Terminal V2)
1. View the value set to F4-12 (Analog Output 6 (Terminal V2) Gain) on the digital operator. A voltage equal to 100% of
the parameter being viewed in F4-11 will be output from analog output 6 (terminal V2).
2. Adjust F4-12 viewing the monitor connected to the analog output 6 (terminal V2).
3. View the value set to F4-13 on the digital operator, analog output 6 (terminal V2) will output a voltage equal to 0% of
the parameter being set in F4-11.
4. Adjust F4-13 viewing the output signal on the analog output 6 (terminal V2).
u F5: Contact Output Card Settings
These parameters set the drive for operation with the contact output option card DO-A3. This section describes
parameters that govern operation with a contact output option card. Refer to the instruction manual packaged with the
option card for specific details on installation, wiring, input signal level selection, and parameter setup.
F5-01 through F5-08: Contact Output Option Card Terminal Function Selection
n
When F5-09 = 2, the parameters listed in the table below are used to assign functions to the output terminals on the
option card.
No.
F5-01
F5-02
F5-03
F5-04
F5-05
F5-06
F5-07
F5-08
F5-09: DO-A3 Output Mode Selection
n
Determines how the DO-A3 option card works with the drive.
No.
F5-09
Note: Refer to TOBP C730600 41 YASKAWA AC Drive-Option Card DO-A3 Installation Manual for more details on F5-09 settings.
Setting 0: Separate output functions for each of 8 terminals
Setting 1: Binary output
Setting 2: Output functions assigned by F5-01 through F5-08
168
Name
Analog Output 6 (Terminal V2) Signal Level Selection
Name
Contact Output 1 (Terminal P1-PC Output Selection)
Contact Output 2 (Terminal P2-PC Output Selection)
Contact Output 3 (Terminal P3-PC Output Selection)
Contact Output 4 (Terminal P4-PC Output Selection)
Contact Output 5 (Terminal P5-PC Output Selection)
Contact Output 6 (Terminal P6-PC Output Selection)
Contact Output 7 (Terminal M1-M2 Output Selection)
Contact Output 8 (Terminal M3-M4 Output Selection)
Parameter Name
DO-A3 Output Mode Selection
Setting Range
0 or 1
Setting Range
0 to 1FF
0 to 1FF
0 to 1FF
0 to 1FF
0 to 1FF
0 to 1FF
0 to 1FF
0 to 1FF
Setting Range
0 to 2
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Default
1
Default
0: During run
1: Zero speed
2: Frequency (speed) agree
4: Frequency (FOUT) detection 1
6: Drive ready
37: During frequency output
F: Not used
F: Not used
Default
0