u E4: Motor 2 Parameters
E4 parameters contain the motor data for motor 2. These parameters are usually set automatically during the
Auto-Tuning process (Rotational Auto-Tuning, Stationary Auto-Tuning). If Auto-Tuning cannot be performed, refer to
the FSDrive-MV1000 Instructions (Manual No. TOEP C710687 02).
E4-01: Motor 2 Rated Current
n
Set E4-01 to the full load amps (FLA) stamped on the nameplate of motor 2. This value is used for motor protection and
to calculate torque limits. If Auto-Tuning completes successfully, the value entered in T1-04 will automatically be saved
to E4-01.
No.
E4-01
<1> For details on the default settings, refer to
Note: If the motor rated current in E4-01 is set lower than the motor no-load current in E4-03, then a parameter setting error will occur
(oPE02). E4-03 must be set correctly to prevent this error.
E4-02: Motor 2 Rated Slip
n
This parameter sets the motor 2 rated slip frequency. Slip compensation is based on this value. The drive calculates this
value automatically during Auto-Tuning (Rotational Auto-Tuning and Stationary Auto-Tuning).
For information on calculating the motor rated slip, refer to
No.
E4-02
<1> For details on the default settings, refer to
E4-03: Motor 2 Rated No-Load Current
n
Set the no-load current for motor 2 in amperes when operating at the rated frequency and the no-load voltage. The drive
sets E2-03 during the Auto-Tuning process (Rotational Auto-Tuning and Stationary Auto-Tuning). The motor no-load
current listed in the motor test report can also be entered to E2-03 manually. Contact the motor manufacturer to receive a
copy of the motor test report.
No.
E4-03
Motor 2 Rated No-Load Current
<1> For details on the default settings, refer to
E4-04: Motor 2 Motor Poles
n
Set the pole number of motor 2 to E4-04. If Auto-Tuning completes successfully, the entered value in T1-06 will be
automatically saved in E4-04.
No.
E4-04
E4-05: Motor 2 Line-to-Line Resistance
n
Sets the line-to-line resistance for the motor 2 stator winding. If Auto-Tuning completes successfully, this value is
automatically calculated. Enter this value as line-to-line and not for each motor phase. Refer to
Line-to-Line Resistance on page 158
No.
E4-05
Motor 2 Line-to-Line Resistance
<1> For details on the default settings, refer to
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Name
Motor 2 Rated Current
Defaults by Drive Model Selection (o2-04) on page
Name
Motor 2 Rated Slip
Defaults by Drive Model Selection (o2-04) on page
Name
Defaults by Drive Model Selection (o2-04) on page
Name
Motor 2 Motor Poles
to manually enter this parameter setting.
Name
Defaults by Drive Model Selection (o2-04) on page
Setting Range
10% to 200% of the drive rated current.
E2-02: Motor Rated Slip on page
Setting Range
0.00 to 20.00 Hz
Setting Range
0 to [E4-01]
Setting Range
2 to 48
Setting Range
0.000 to 65.000 W
2.5 E: Motor Parameters
Default
Determined by o2-04
87.
157.
Default
Determined by o2-04
87.
Default
Determined by o2-04
87.
Default
4
E2-05: Motor
Default
Determined by o2-04
87.
<1>
<1>
<1>
<1>
161