YASKAWA FSDrive-MV1000 Parameter Manual page 36

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

1.3 Parameter Table
No.
Name
(Addr.)
d1-11
Frequency
(28CH)
Reference 11
d1-12
Frequency
(28DH)
Reference 12
d1-13
Frequency
(28EH)
Reference 13
d1-14
Frequency
(28FH)
Reference 14
d1-15
Frequency
(290H)
Reference 15
d1-16
Frequency
(291H)
Reference 16
d1-17
Jog Frequency
(292H)
Reference
Frequency
d2-01
Reference Upper
(289H)
Limit
Frequency
d2-02
Reference Lower
(28AH)
Limit
Master Speed
d2-03
Reference Lower
(293H)
Limit
d3-01
Jump Frequency 1
(294H)
d3-02
Jump Frequency 2
(295H)
d3-03
Jump Frequency 3
(296H)
d3-04
Jump Frequency
(297H)
Width
Frequency
d4-01
Reference Hold
(298H)
Function Selection
d4-03
Frequency
(2AAH)
Reference Bias Step
(Up/Down 2)
36
All Modes
Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes
Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes
Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes
Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes
Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes
Sets the frequency reference for the drive. Setting units are determined
according to the frequency reference selection/display unit setting (o1-03).
All Modes
Sets the Jog frequency reference. Setting units are determined by parameter
o1-03.
d2: Frequency Upper/Lower Limits
All Modes
Sets the frequency reference upper limit as a percentage of the maximum
output frequency.
All Modes
Sets the frequency reference lower limit as a percentage of the maximum
output frequency.
All Modes
Sets the lower limit for frequency references from analog inputs as a
percentage of the maximum output frequency.
d3: Jump Frequency
All Modes
Eliminates problems with resonant vibration of the motor/machine by
avoiding continuous operation in predefined frequency ranges. The drive
accelerates and decelerates the motor through the prohibited frequency
ranges.
Setting 0.0 disables this function.
Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.
All Modes
Sets the dead-band width around each selected prohibited frequency
reference point.
d4: Frequency Reference Hold and Up/Down 2 Function
All Modes
0: Disabled. Drive starts from zero when the power is switched on.
1: Enabled. At power up, the drive starts the motor at the Hold frequency
that was saved.
All Modes
Sets the bias added to the frequency reference when the Up 2 and Down 2
contact inputs are enabled (H1-
Description
common_
common_
common_
common_
common_
common_
common_
= 75, 76).
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Setting
Default: 0.00 Hz
Min: 0.00 Hz
Max: 120.00 Hz
<20>
Default: 0.00 Hz
Min: 0.00 Hz
Max: 120.00 Hz
<20>
Default: 0.00 Hz
Min: 0.00 Hz
Max: 120.00 Hz
<20>
Default: 0.00 Hz
Min: 0.00 Hz
Max: 120.00 Hz
<20>
Default: 0.00 Hz
Min: 0.00 Hz
Max: 120.00 Hz
<20>
Default: 0.00 Hz
Min: 0.00 Hz
Max: 120.00 Hz
<20>
Default: 6.00 Hz
Min: 0.00 Hz
Max: 120.00 Hz
<20>
common_
Default: 100.0%
Min: 0.0%
Max: 110.0%
Default: 0.0%
common_
Min: 0.0%
Max: 110.0%
Default: 0.0%
Min: 0.0
Max: 110.0%
Default: 0.0 Hz
Min: 0.0 Hz
Max: 120.0 Hz
<20>
Default: 1.0 Hz
Min: 0.0 Hz
Max: 20.0 Hz
Default: 0
Min: 0
Max: 1
Default: 0.00 Hz
Min: 0.00 Hz
Max: 99.99 Hz
Page
140
140
140
140
140
140
140
142
142
142
143
143
143
143
144
146