YASKAWA FSDrive-MV1000 Parameter Manual page 58

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

1.3 Parameter Table
H2-
Function
Setting
2F
Maintenance Period
30
During Torque Limit
31
During Speed Limit
During Speed Limit in Torque
32
Control
37
During Frequency Output
38
Drive Enabled
39
Watt Hour Pulse Output
Cooling Fan, Transformer
Abnormal Temperature
3A
Rise
3C
LOCAL/REMOTE Status
3D
During Speed Search
3E
PID Feedback Low
3F
PID Feedback High
Close Command for
40
Commercial Power Supply
Side Breaker
Close Command for Drive
41
Secondary Side Breaker
Completion Signal for
42
Synchronous Transfer
4C
During Fast Stop
4D
oH Pre-Alarm Time Limit
60
Internal Cooling Fan Alarm
58
H2 Contact Output Settings
All Modes
Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay may
require maintenance.
V/f
OLV
Closed: When the torque limit has been reached.
V/f
OLV
Closed: Speed limit has been reached.
V/f
OLV
Closed: Speed limit has been reached while using Torque Control.
All Modes
Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial
Excitation is being performed.
Closed: Drive is running the motor (not in a baseblock state and DC Injection is not
being performed).
All Modes
Closed: Contact input set for "Drive enable" is closed (H1-
All Modes
Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate the
kWh count.
All Modes
Closed: No abnormal temperature rise in the cooling fans or transformers has occurred.
All Modes
Open: REMOTE
Closed: LOCAL
All Modes
Closed: Speed Search is being executed.
All Modes
Closed: PID feedback level is too low.
All Modes
Closed: The PID feedback level is too high.
All Modes
Open: Open Command
Closed: Close Command
Note: Use this setting if the Synchronous Transfer is used.
All Modes
Open: Open Command
Closed: Close Command
Note: Use this setting if the Synchronous Transfer is used.
All Modes
Open: The Synchronous Transfer is in progress or it is not used.
Closed: The Synchronous Transfer to commercial power supply completed.
Note: Use this setting if the Synchronous Transfer is used.
All Modes
Closed: A Fast Stop command has been entered from the operator or input terminals.
All Modes
Closed: oH pre-alarm time limit has passed.
All Modes
Closed: Internal cooling fan alarm
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Description
common_
CLV
common
CLV
common
CLV
common
common_
common_
common_
common_
common_
common
common_
common_
common_
common_
common_
common_
common_
common_
Page
189
189
190
190
190
190
= 6A)
190
190
190
190
190
191
191
191
191
191
191
191