o1-04: V/f Pattern Display Unit (CLV)
n
Determines the units used for the frequency reference when setting parameters that create the V/f pattern: E1-04, E1-06,
E1-07, E1-09, and E1-11. For motor 2, this includes parameters E3-04, E3-06, E3-07, E3-09, and E3-11.
Enabled only in CLV control mode.
When o1-04 = 1, this parameter is set in r/min units with the value in E2-04 as the number of motor poles.
No.
o1-04
V/f Pattern Display Unit
<1> For details on the default settings, refer to
Setting 0: Hz
Setting 1: r/min
Note: For motor 2, o1-04 can only be set to 0 for Hertz.
o1-10: User-Set Display Units Maximum Value
n
Determines the display value that is equal to the maximum output frequency.
No.
o1-10
User-Set Display Units Maximum Value
o1-11: User-Set Display Units Decimal Display
n
Determines how many decimal points should be used to set and display the frequency reference.
No.
o1-11
User-set Display Units Decimal Display
Setting 0: No decimal point
Setting 1: One decimal point
Setting 2: Two decimal points
Setting 3: Three decimal points
u o2: Digital Operator Keypad Functions
These parameters determine the functions assigned to the operator keys.
o2-01: LO/RE (LOCAL/REMOTE) Key Function Selection
n
Parameter o2-01 determines whether the LO/RE key on the digital operator will be enabled or not for switching between
LOCAL and REMOTE.
No.
o2-01
LO/RE Key Function Selection
Setting 0: Disabled
The LO/RE key is disabled.
Setting 1: Enabled
The LO/RE switches between LOCAL and REMOTE operation. Switching is possible during stop only. When LOCAL
is selected, the LED indicator on the LO/RE key will light up.
WARNING! Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching
from LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Check all mechanical or
electrical connections thoroughly before making any setting changes to o2-01 and b1-07.
combinations for o2-01 and b1-07.
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Name
0 or 1
Control Mode Dependent Parameter Default Values on page
Name
1 to 60000
Name
0 to 3
Name
0, 1
2.10 o: Operator Related Settings
Setting Range
Setting Range
Setting Range
Setting Range
Default
Determined by A1-02
<1>
84.
Default
Determined by o1-03
Default
Determined by o1-03
Default
1
Table 2.30
lists the setting
233