2.2 b: Application
DC Injection Braking time is determined by the value set to b2-04 and by the output frequency at the time the Stop
command is input or the Run command is removed. It can be calculated by:
Figure 2.3
Note: If an overcurrent (OC) fault occurs during DC Injection Braking to Stop, lengthen the minimum baseblock time (L2-03) until the
fault no longer occurs.
Setting 3: Coast to Stop with Timer
When a Stop command is input or the Run command is removed, the drive will turn off its output and the motor will
coast to a stop. The drive will not start if a Run command is input before the time t (C1-02) has expired. Cycle the Run
command that was activated during time t after t has expired to start the drive.
Figure 2.4
The wait time t is determined by the output frequency when the Stop command is input or the Run command is removed
and by the active deceleration time.
Figure 2.5
104
DC Injection brake time
DC Injection braking time
b2-04 10
b2-04
10%
Figure 2.3 DC Injection Braking Time Depending on Output Frequency
Run command
ON
Output
frequency
Figure 2.4 Coast to Stop with Timer
Run wait time t
Active deceleration time
Min Baseblock Time (L2-03)
Min output
Figure 2.5 Run Wait Time Depending on Output Frequency
(b2-04) × 10 × Output frequency
=
Max. output frequency (E1-04)
Output frequency when
Stop command was entered
OFF
ON
Drive output shut off
Run wait time t
Output frequency
frequency
when Stop command
was entered