YASKAWA FSDrive-MV1000 Parameter Manual page 164

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

2.6 F: Option Settings
Parameter F1-03 Settings:
Setting 0: Ramp to stop (uses the deceleration time set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop time set to C1-09)
Setting 3: Alarm only
Note: Due to potential damage to motor and machinery, the "Alarm only" setting should be used only under special circumstances.
F1-04, F1-10, F1-11: Operation at Speed Deviation (dEv), Detection Level, Delay Time
n
A speed deviation error (dEv) is triggered when the difference between the frequency reference and the speed feedback
exceeds the value set in F1-10 for longer than the time set in F1-11. The stopping method when a speed deviation fault
occurs can be selected in parameter F1-04.
No.
F1-04
Operation Selection at Deviation (dEv)
F1-10
Excessive Speed Deviation Detection Level
F1-11
Excessive Speed Deviation Detection Delay Time
Settings for Parameter F1-04:
Setting 0: Ramp to stop (uses the deceleration time set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop time set to C1-09)
Setting 3: Alarm only (drive continues operating while "dEv" flashes on the screen)
F1-05, F1-32: PG 1, PG 2 Rotation Selection
n
Determines the direction indicated by the pulses from the PG feedback encoder for motor 1 and motor 2.
Refer to PG option card instruction manual for details on how to set the direction for the PG encoder and the motor.
No.
F1-05
F1-32
<1> For details on the default settings, refer to
Setting 0: A pulse leads with Forward run command
Setting 1: B pulse leads with Forward run command
F1-06, F1-35: PG 1, PG 2 Division Rate for PG Pulse Monitor
n
Sets the division ratio for the pulse monitor used for the PG option card installed to port CN5-B or CN5-C. By setting
xyz as a three-digit number, the division ratio becomes = [(1 + x) / (y × 10 + z)]. If only using the A pulse for one track
input, then the input ratio will be 1:1, regardless of the setting of F1-06 or F1-35.
Example:
When the division ratio is 1;
F1-06 = 1, division ratio = (1 + 0)/(0 × 10 + 1) = 1
When the division ratio is 2/16 (1/8);
F1-06 = 116, division ratio = (1 + 1)/(1 × 10 + 6) = 2/16
No.
F1-06
PG 1 Division Rate for PG Pulse Monitor
F1-35
PG 2 Division Rate for PG Pulse Monitor
164
Parameter Name
Parameter Name
PG 1 Rotation Selection
PG 2 Rotation Selection
Control Mode Dependent Parameter Default Values on page
Parameter Name
Option Port
Setting Range
CN5-B, CN5-C
0 to 3
CN5-B, CN5-C
0 to 50%
CN5-B, CN5-C
0.0 to 10.0 s
Option Port
Setting Range
CN5-C
0, 1
CN5-B
0, 1
Option Port
Setting Range
CN5-C
1 to 132 (1 to
1 to 132 (1 to
CN5-B
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Default
3
10%
0.5 s
Default
Determined by A1-02
Determined by A1-02
84.
Default
1
)
1
32
1
)
1
32
<1>
<1>