2.2 b: Application
b5-18: PID Setpoint Selection
n
Enables or disables parameter b5-19 for the PID setpoint.
No.
b5-18
Setting 0: Disabled
Parameter b5-19 is not used as the PID setpoint.
Setting1: Enabled
Parameter b5-19 is used as the PID setpoint.
b5-19: PID Setpoint Value
n
Used as the PID setpoint if parameter b5-18 = 1.
No.
b5-19
b5-20: PID Setpoint Scaling
n
Determines the units for the PID Setpoint Value (b5-19) and monitors U5-01 and U5-04.
No.
b5-20
Setting 0: 0.01 Hz units
The setpoint and PID monitors are displayed in Hz with a resolution of 0.01 Hz.
Setting 1: 0.01% units (100% = max. output frequency)
The setpoint and PID monitors are displayed as a percentage with a resolution of 0.01%.
Setting 2: r/min
The setpoint and PID monitors are displayed in r/min with a resolution of 1 r/min.
Setting 3: User Defined
Parameters b5-38 and b5-39 determine the units and resolution used to display the values for the setpoint in b5-19, and
PID monitors U1-01 and U1-04.
b5-34: PID Output Lower Limit
n
Sets the minimum possible PID controller output as a percentage of the maximum output frequency (E1-04). The lower
limit is disabled when set to 0.00%
No.
b5-34
b5-35: PID Input Limit
n
Sets the maximum allowed PID input as a percentage of the maximum output frequency (E1-04). Parameter b5-35 acts as
a bipolar limit.
No.
b5-35
124
Name
PID Setpoint Selection
Name
PID Setpoint Value
Name
PID Setpoint Scaling
Name
PID Output Lower Limit
Name
PID Input Limit
Setting Range
0 or 1
Setting Range
0.00 to 100.00%
Setting Range
0 to 3
Setting Range
-100.0 to 100.0%
Setting Range
0 to 1000.0%
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Default
0
Default
0.00%
Default
1
Default
0.0%
Default
1000.0%