Setting 0: ENTER key required
Every time the frequency reference is changed using the digital operator, the ENTER key must be pressed for the drive to
accept the change.
Setting 1: ENTER key not required
The output frequency changes immediately when the reference is changed with the up or down arrow keys on the digital
operator. The ENTER key does not need to be pressed. The frequency reference (Fref) is saved to memory after
remaining unchanged for 5 s.
o2-06: Operation Selection when Digital Operator is Disconnected
n
Determines whether the drive will stop when the digital operator is removed in LOCAL mode or when b1-02 or b1-16 is
set to 0. When the operator is reconnected, the display will indicate that it was disconnected.
No.
Operation Selection when Digital Operator
o2-06
Setting 0: Disabled
The operation is continued.
Setting 1: Trigger a fault
The operation is stopped and an "oPr" fault is triggered. The motor coasts to stop.
o2-07: Motor Direction at Power Up when Using Operator
n
Determines the direction in which the motor will rotate after the drive is powered up and the Run command is given from
the digital operator.
Note: This parameter is effective only when the Run command is set to be given from the digital operator (b1-02, b1-16 = 0).
No.
Motor Direction at Power Up when Using
o2-07
Setting 0: Forward
Setting 1: Reverse
o2-11: Reference Voltage for Input Voltage Detection
n
Sets the primary voltage rating of the transformer.
No.
Reference Voltage for Input Voltage
o2-11
<1> For details on the default settings, refer to
u o3: Copy Function
o3-01: Copy Function Selection
n
These parameters control the Copy function of the digital operator. The Copy function lets the user store all parameter
settings into the memory of the digital operator, and transfer those settings to other drives (this feature requires that the
other drives be the same model, capacity, and have the same control mode setting). Refer to the FSDrive-MV1000
Instructions (Manual No. TOEP C710687 02) for a description of errors and displays.
No.
o3-01
Copy Function Selection
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Name
is Disconnected
Name
Operator
Name
Detection
Defaults by Drive Model Selection (o2-04) on page
Name
Setting Range
0, 1
Setting Range
0, 1
Setting Range
0 to 20000 V
Setting Range
0 to 3
2.10 o: Operator Related Settings
Default
0
Default
0
Default
Determined by o2-04
87.
Default
0
<1>
235