YASKAWA FSDrive-MV1000 Parameter Manual page 196

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

2.7 H: Terminal Functions
Setting 5: Accel/decel time gain
Adjusts the gain level for the acceleration and deceleration times set in parameters C1-01 through C1-08.
The acceleration time used by the drive is calculated by multiplying this gain level by C1-
× Accel/decel time gain = Drive accel/decel time
C1-
Figure 2.66
Setting 6: DC Injection Braking current
The current level used for DC Injection Braking. Set as a percentage of the maximum output current using.
When setting the bias by parameter, however, make the setting as a percentage of the motor rated current.
Note also that the DC injection braking current is limited by the motor rated current value.
Figure 2.67
Setting 7: Torque Detection level
Using this setting, the overtorque/undertorque detection level for Torque Detection Selection 1 (L6-01) can be set by an
analog input. The analog input will replace the level set for Torque Detection Level 1 (L6-02). An analog input of 100%
(10 V) will set a torque detection level equal to 100% drive rated current / motor rated torque. Adjust the analog input
gain if higher detection level settings are required. Refer to
Setting 8: Stall Prevention level
This setting allows an analog input signal to adjust the Stall Prevention level.
characteristics. The drive will use either the Stall Prevention level set in L3-06 or the level coming from the analog input
terminal that has been selected, whichever value is lower.
Figure 2.68
Setting 9: Output frequency lower limit level
The user can adjust the lower limit of the output frequency using an analog input signal.
Setting B: PID feedback
An input set for this function supplies the PID feedback value. This setting requires PID operation to be enabled in b5-01.
Refer to
PID Feedback Input Methods on page
196
100%
50%
20%
10%
0
1 V 2 V
5 V
Figure 2.66 Accel/Decel Time Gain with Analog Input Terminal
DC Injection Braking Current Level
common_TMonly
Figure 2.67 DC Injection Braking Current Using an Analog Input Terminal
Stall Prevention Level during Run
100%
30%
0
30%
Figure 2.68 Stall Prevention During Run Using an Analog Input Terminal
Acceleration/deceleration gain from 1 to 10 V
(10 V)
=       
Input Voltage (V)
common_TMonly
10 V
100%
Drive Rated
Current
0
10 V
L6: Torque Detection on page 213
common_TMonly
Analog Input Value of Input Terminal
100%
116.
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
as follows:
× 10 (%)
for details.
Figure 2.68
shows the setting

Advertisement

Table of Contents
loading

Table of Contents