2.5 E: Motor Parameters
u E3: V/f Pattern for Motor 2
These parameters set the V/f pattern used for motor 2. Refer to
switching motors.
E3-01: Motor 2 Control Mode Selection
n
Selects the control mode for motor 2.
Note: 1. E3-01 dependent parameters are reset to the default settings when E3-01 is changed.
2. Protection from motor overload (oL1) is determined by L1-01, just as it is for motor 1.
No.
E3-01
Setting 0: V/f Control
Setting 2: Open Loop Vector Control
Setting 3: Closed Loop Vector Control
E3-04 to E3-13
n
Parameters E3-04 through E3-13 set up the V/f pattern used for motor 2 as shown in
No.
E3-04
E3-05
E3-06
E3-07
E3-08
Motor 2 Mid Output Frequency Voltage
E3-09
E3-10
E3-11
E3-12
Motor 2 Mid Output Frequency Voltage 2
E3-13
<1> Default setting is determined by the control mode selected for motor 2 (E3-01).
<2> The drive sets this value when Auto-Tuning is performed (Rotational Auto-Tuning and Stationary Auto-Tuning).
<3> Parameter ignored when E3-11 and E3-12 are set to 0.0.
<4> When Auto-Tuning for motor 2 is performed, E3-13 and E3-05 will be set to the same value.
<5> Default setting is determined by A1-02, Control Method Selection.
Figure 2.43
Note: 1. The following conditions must be true when setting up the V/f pattern: E3-09 £ E3-07 < E3-06 ≤ E3-11 ≤ E3-04
2. To make the V/f pattern a straight line at a frequency lower than E3-06, set E3-09 = E3-07. With this setting, E3-08 is disregarded.
3. Parameters E3-04 through E3-13 are reset to their default values when the drive is initialized.
4. E3-11, E3-12, and E3-13 rarely need to be changed, and should only be used to fine-tune the V/f pattern in the constant output range.
160
Name
Motor 2 Control Mode Selection
Name
Motor 2 Maximum Output Frequency
Motor 2 Maximum Voltage
Motor 2 Base Frequency
Motor 2 Mid Output Frequency
Motor 2 Minimum Output Frequency
Motor 2 Minimum Output Voltage
Motor 2 Mid Output Frequency 2
Motor 2 Base Voltage
Output (V)
E3-05
E3-12
E3-13
E3-08
E3-10
Figure 2.43 V/f Pattern for Motor 2
Setting 16: Motor 2 Selection on page 176
0, 2, 3
40.0 to 120.0 Hz
0 to 13000 V
0.0 to 120.0 Hz
0.0 to 120.0 Hz
0 to 13000 V
0.0 to 120.0 Hz
0 to 13000 V
0.0 to120.0 Hz
0 to 13000 V
0 to 13000 V
common_TMonly
E3-09
E3-06 E3-11 E3-04
E3-07
Frequency (Hz)
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Setting Range
Figure
2.43.
Setting Range
for details on
Default
2
Default
<1>
<1>
<1>
<1>
<1>
<1>
<1>
0.0 Hz
<3>
0 V
<2> <3> <5>
0 V
<2> <4> <5>