No.
Name
(Addr.)
F6-62
DeviceNet
(3DDH)
Heartbeat Interval
F6-63
DeviceNet Network
(3DEH)
MAC ID
F6-64 to
F6-71
Reserved
(3DFH to
3C8H)
• F7-01 through F7-42 are common settings used for Modbus TCP/IP, and EtherNet/IP option cards. Other parameters in the F7 group are used for
communication protocol specific settings.
• For more details on a specific option card, refer to the instruction manual for the option card.
F7-01
(3E5)
IP Address 1
<47> <48>
<49>
F7-02
(3E6)
IP Address 2
<47> <48>
<49>
F7-03
(3E7)
IP Address 3
<47> <48>
<49>
F7-04
(3E8)
IP Address 4
<47> <48>
<49>
F7-05
(3E9)
Subnet Mask 1
<49>
F7-06
(3EA)
Subnet Mask 2
<49>
F7-07
(3EB)
Subnet Mask 3
<49>
F7-08
(3EC)
Subnet Mask 4
<49>
F7-09
(3ED)
Gateway Address 1
<49>
F7-10
(3EE)
Gateway Address 2
<49>
F7-11
(3EF)
Gateway Address 3
<49>
F7-12
(3E0)
Gateway Address 4
<49>
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
All Modes
Sets the heartbeat interval for DeviceNet communications.
All Modes
Saves and monitors the settings 0 to 63 of F6-50 (DeviceNet MAC Address).
All Modes
Reserved for Dynamic I/O Assembly Parameters.
F7: Communication Option Cards
All Modes
Sets the static/fixed IP address.
Parameter F7-01 sets the most significant octet.
All Modes
Sets the static/fixed IP address.
Parameter F7-02 sets the second most significant octet.
All Modes
Sets the static/fixed IP address.
Parameter F7-03 sets the third most significant octet.
All Modes
Sets the static/fixed IP address.
Parameter F7-04 sets the fourth most significant octet.
All Modes
Sets the static/fixed Subnet Mask.
Parameter F7-05 sets the most significant octet.
All Modes
Sets the static/fixed Subnet Mask.
Parameter F7-06 sets the second most significant octet.
All Modes
Sets the static/fixed Subnet Mask.
Parameter F7-07 sets the third most significant octet.
All Modes
Sets the static/fixed Subnet Mask.
Parameter F7-08 sets the fourth most significant octet.
All Modes
Sets the static/fixed Gateway address.
Parameter F7-09 sets the most significant octet.
All Modes
Sets the static/fixed Gateway address.
Parameter F7-10 sets the second most significant octet.
All Modes
Sets the static/fixed Gateway address.
Parameter F7-11 sets the third most significant octet.
All Modes
Sets the static/fixed Gateway address.
Parameter F7-12 sets the fourth most significant octet.
Description
1.3 Parameter Table
Setting
Default: 0
common_
Min: 0
Max: 10
Default: 0
common_
Min: 0
Max: 63
common_
Default: 192
common_
TMonly
Min: 0
Max: 255
Default: 168
common_
TMonly
Min: 0
Max: 255
Default: 1
common_
TMonly
Min: 0
Max: 255
Default: 20
common_
TMonly
Min: 0
Max: 255
Default: 255
common_
TMonly
Min: 0
Max: 255
Default: 255
common_
TMonly
Min: 0
Max: 255
common_
Default: 255
TMonly
Min: 0
Max: 255
Default: 0
common_
TMonly
Min: 0
Max: 255
Default: 192
common_
TMonly
Min: 0
Max: 255
Default: 168
common_
TMonly
Min: 0
Max: 255
Default: 1
common_
TMonly
Min: 0
Max: 255
Default: 1
common_
TMonly
Min: 0
Max: 255