L6-08: Mechanical Weakening Detection Operation
n
Sets the speed range to detect mechanical weakening and the action to take when mechanical weakening is detected.
No.
L6-08
Mechanical Weakening Detection Operation
Setting 0: Disabled
Setting 1: Continue running if the speed is greater than L6-09 (signed) (alarm)
Detection when the speed is above L6-09 (signed). Upon detection operation continues, but an oL5 alarm is output.
Setting 2: Continue running if the speed is greater than L6-09 (alarm)
Detection when the speed is above L6-09 (unsigned). Upon detection operation continues, but an oL5 alarm is output.
Setting 3: Stop when motor speed is greater than L6-09 (signed)
Detection when the speed is above L6-09 (signed). Upon detection operation is stopped and an oL5 fault is output.
Setting 4: Stop when Motor Speed is Greater than L6-09
Detection when the speed is above L6-09 (unsigned). Upon detection operation is stopped and an oL5 fault is output.
Setting 5: Continue running if the speed is less than L6-09 (signed) (alarm)
Detection when the speed is below L6-09 (signed). Upon detection operation continues, but a UL5 alarm is output.
Setting 6: Continue running if the speed is less than L6-09 (alarm)
Detection when the speed is below L6-09 (unsigned). Upon detection operation continues, but a UL5 alarm is output.
Setting 7: Stop when Motor Speed is less than L6-09 (signed)
Detection when the speed is below L6-09 (signed). Upon detection operation is stopped and a UL5 fault is output.
Setting 8: Stop when motor speed is less than L6-09
Detection when the speed is below L6-09 (unsigned). Upon detection the operation is stopped and a UL5 fault is output.
L6-09: Mechanical Weakening Detection Speed Level
n
Sets the speed level for Mechanical Weakening Detection.
No.
L6-09
Mechanical Weakening Detection Speed Level
The value is set as a percentage of the maximum frequency. If L6-08 is set for unsigned speed detection (L6-08 = 2, 4, 6,
8) then the absolute value of L6-09 is used (negative settings are treated as positive values).
L6-10: Mechanical Weakening Detection Time
n
Sets the time permitted for the situation selected in parameter L6-08 to arise before mechanical weakening is detected.
No.
L6-10
Mechanical Weakening Detection Time
L6-11: Mechanical Weakening Detection Start Time
n
Sets the drive cumulative operation time at which Mechanical Weakening Detection is activated. If U4-01 reaches the
L6-11 value, the function is activated.
No.
L6-11
Mechanical Weakening Detection Start Time
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Name
Name
Name
Name
Setting Range
0 to 8
Setting Range
-110.0 to 110.0%
Setting Range
0.0 to 10.0 s
Setting Range
0 to 65535 h
2.8 L: Protection Functions
Default
0
Default
110.0%
Default
0.1 s
Default
0 h
215