H2-
Function
Setting
F
Through Mode
10
Minor Fault
11
Fault Reset Command Active
12
Timer Output
13
Speed Agree 2
14
User-set Speed Agree 2
15
Frequency Detection 3
16
Frequency Detection 4
17
Torque Detection 1 (N.C.)
18
Torque Detection 2 (N.O.)
19
Torque Detection 2 (N.C.)
1A
During Reverse
1B
During Baseblock (N.C.)
1C
Motor 2 Selection
1D
During Regeneration
1E
Restart Enabled
1F
Motor Overload Alarm (oL1)
Drive Overheat Pre-Alarm
20
(oH)
21
User-Set Alarm
Mechanical Weakening
22
Detection (N.O.)
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
H2 Contact Output Settings
All Modes
Set this value when using the terminal in the pass-through mode.
All Modes
Closed: An alarm has been triggered, or the IGBTs have reached 90% of their expected
life span.
All Modes
Closed: A command has been entered to clear a fault via the contact input terminals or
from the serial network.
All Modes
Closed: Timer output.
All Modes
Closed: When drive output frequency equals the frequency reference ± L4-04.
All Modes
Closed: When the drive output frequency is equal to the value in L4-03 ± L4-04.
All Modes
Closed: When the drive output frequency is less than or equal to the value in
L4-03 ± L4-04.
All Modes
Closed: When the output frequency is greater than or equal to the value in
L4-03 ± L4-04.
All Modes
Open: Overtorque or undertorque has been detected.
All Modes
Closed: Overtorque or undertorque has been detected.
All Modes
Open: Overtorque or undertorque has been detected.
All Modes
Closed: Drive is running in the reverse direction.
All Modes
Open: Drive has entered the baseblock state (no output voltage).
All Modes
Closed: Motor 2 is selected by a contact input (H1-
V/f
OLV
Closed: Motor is regenerating energy into the drive.
All Modes
Closed: An automatic restart is performed
All Modes
Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers this
alarm.
All Modes
Closed: Thermistor temperature exceeds the parameter L8-02 value.
All Modes
Closed: Alarm selected to H2-18 occurred.
Note: This setting is available from the drive software versions S0108 and later.
All Modes
Closed: Mechanical weakening detected.
Description
common_
common_
common_
common_
common_
common_
common_
common_
common_
common_
common_
common_
common_
common
= 16).
CLV
common
common_
common_
common_
common_
common_
1.3 Parameter Table
Page
186
186
186
186
186
187
187
188
186
186
186
188
189
189
189
189
189
189
189
189
57