YASKAWA FSDrive-MV1000 Parameter Manual page 40

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

1.3 Parameter Table
No.
Name
(Addr.)
Motor Iron-Core
E2-08
Saturation
(315H)
Coefficient 2
E2-09
Motor Mechanical
(316H)
Loss
Motor Iron Loss for
E2-10
Torque
(317H)
Compensation
E2-11
Motor Rated Power Sets the motor rated capacity in kW (1 HP = 0.746 kW).
(318H)
E3-01
Motor 2 Control
(319H)
Mode Selection
E3-04
Motor 2 Maximum
(31AH)
Output Frequency
E3-05
Motor 2 Maximum
(31BH)
Voltage
E3-06
Motor 2 Base
(31CH)
Frequency
E3-07
Motor 2 Mid Output
(31DH)
Frequency
E3-08
Motor 2 Mid Output
(31EH)
Frequency Voltage
E3-09
Motor 2 Minimum
(31FH)
Output Frequency
E3-10
Motor 2 Minimum
(320H)
Output Voltage
E3-11
Motor 2 Mid Output
(345H)
Frequency 2
<24>
E3-12
Motor 2 Mid Output
(346H)
Frequency Voltage 2
<24>
E3-13
Motor 2 Base
(347H)
Voltage
E4-01
Motor 2 Rated
(321H)
Current
E4-02
Motor 2 Rated Slip
(322H)
40
V/f
OLV
Sets the motor iron saturation coefficient at 75% of magnetic flux.
Automatically set during Auto-Tuning.
V/f
OLV
Sets the motor mechanical loss as a percentage of motor rated power (W).
Adjust the setting in the following circumstances:
• When there is a large amount of torque loss due to motor bearing friction
• When there is a large amount of torque loss in a fan or pump application
V/f
OLV
Sets the motor iron loss.
All Modes
Automatically set during Auto-Tuning.
E3: V/f Pattern for Motor 2
All Modes
0: V/f Control
2: Open Loop Vector Control
3: Closed Loop Vector Control
All Modes
To set linear V/f characteristics, set the same values for E3-07 and E3-09. In
this case, the setting for E3-08 will be disregarded. Ensure that the four
frequencies are set according to these rules or an oPE10 fault will occur:
E3-04 ≥ E3-06 > E3-07 ≥ E3-09
Output Voltage (V)
E3-05
E3-12
E3-13
E3-08
E3-10
E3-09
Note: E3-07 and E3-08 are only available in the following
control modes: V/f Control, Open Loop Vector.
E4: Motor 2 Parameters
All Modes
Sets the full load current for motor 2. Automatically set during Auto-Tuning.
All Modes
Sets the rated slip for motor 2. Automatically set during Auto-Tuning.
Description
CLV
CLV
common
CLV
common
E3-07 E3-06 E3-11 E3-04
Frequency (Hz)
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Setting
Default: 0.75
common
Min: E2-07
Max: 0.75
Default: 0.0%
Min: 0.0%
Max: 10.0%
Default:
<6>
Min: 0 W
Max: 65535 W
common_
Default:
<6>
Min: 0 kW
Max: 65000 kW
common_
Default: 2
Min: 0
Max: 3
Default:
<25>
Min: 40.0 Hz
Max: 120.0 Hz
Default:
<25>
Min: 0.0 V
Max: 13000 V
Default:
<25>
common_
Min: 0 Hz
Max: 120 Hz
Default:
<25>
Min: 0.0 Hz
Max: 120.0 Hz
Default:
<25>
Min: 0 V
Max: 13000 V
Default:
<25>
Min: 0.0 Hz
Max: 120.0 Hz
Default:
<25>
Min: 0 V
Max: 13000 V
Default: 0.0
Min: 0.0 Hz
Max: 120.0 Hz
Default: 0 V
Max: 0 V
Max: 13000 V
Default: 0 V
Max: 0 V
Max: 13000 V
Default:
<6>
Min: 10% of drive
common_
rated current
Max: 200% of
drive rated current
Default:
<6>
common_
Min: 0.00 Hz
Max: 20.00 Hz
Page
158
158
158
159
160
160
160
160
160
160
160
160
160
160
<69>
160
161
161