2.2 b: Application
b5-12: 1PID Feedback Loss Detection Selection
n
Enables or disables the feedback loss detection and sets the operation when a feedback loss is detected.
No.
b5-12
Setting 0: Contact output only
A contact output set for "PID feedback low" (H2-
detection level set to b5-13 for the time set to b5-14 or longer. A contact output set for "PID feedback high" (H2-
3F) will be triggered if the PID feedback value is beyond the detection level set to b5-36 for longer than the time set to
b5-37. Neither a fault nor an alarm is displayed on the digital operator and the drive will continue operation. The output
resets when the feedback value leaves the loss detection range.
Setting 1: Feedback Loss Alarm
If the PID feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a "FBL - Feedback
Low" alarm will be displayed and a contact output set for "PID feedback low" (H2-
PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-37, a "FBH - Feedback High" alarm
will be displayed and a contact output set for "PID feedback high" (H2-
an alarm output (H1-
leaves the loss detection range.
Setting 2: Feedback Loss Fault
If the PID feedback value falls below the level set to b5-13 for longer than the time set in b5-14, a "FbL - Feedback Low"
fault will be displayed. If the PID feedback value exceeds the level set to b5-36 for longer than the time set in b5-37, a
"FbH - Feedback High" fault will be displayed. Both events trigger a fault output (H2-
stop the motor.
Setting 3: Contact output only, even if PID is disabled by contact input
Same as b5-12 = 0. Detection remains active when PID is disabled by a contact input (H1-
Setting 4: Feedback loss alarm, even if PID is disabled by contact input
Same as b5-12 = 1. Detection remains active when PID is disabled by a contact input (H1-
Setting 5: Feedback loss fault, even if PID is disabled by contact input
Same as b5-12 = 2. Detection remains active when PID is disabled by a contact input (H1-
b5-13: PID Feedback Low Detection Level
n
Sets the feedback level used for PID feedback low detection. The PID feedback must fall below this level for longer than
the time b5-14 before feedback loss is detected.
No.
b5-13
b5-14: PID Feedback Low Detection Time
n
Sets the time that the PID feedback has to fall below b5-13 before feedback loss is detected.
No.
b5-14
b5-36: PID Feedback High Detection Level
n
Sets the feedback level used for PID feedback high detection. The PID feedback must exceed this level for longer than
the time b5-37 before feedback loss is detected.
No.
b5-36
122
Name
PID Feedback Loss Detection Selection
= 10). The drive will continue operation. The alarm and outputs reset when the feedback value
Name
PID Feedback Loss Detection Level
Name
PID Feedback Loss Detection Time
Name
PID Feedback High Detection Level
Setting Range
= 3E) will be triggered if the PID feedback value is below the
= 3F) will be triggered. Both events trigger
Setting Range
Setting Range
0.0 to 25.5 s
Setting Range
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
0 to 5
= 3E) will be triggered. If the
= E) and cause the drive to
= 19).
= 19).
= 19).
0 to 100%
0 to 100%
Default
0
=
Default
0%
Default
1.0 s
Default
100%