YASKAWA FSDrive-MV1000 Parameter Manual page 52

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

1.3 Parameter Table
H1-
Function
Setting
14
Fault Reset
15
Fast Stop (N.O.)
16
Motor 2 Selection
17
Fast Stop (N.C.)
18
Timer Function Input
19
PID Disable
1A
Accel/Decel Time Selection 2 Used in conjunction with an input terminal set for "Accel/decel time selection 1"
1B
Program Lockout
1E
Reference Sample Hold
20 to 2F
External Fault
30
PID Integral Reset
31
PID Integral Hold
32
Multi-Step Speed Reference 4 The values set in d1-01 to d1-16 (frequency references) can be selected according to the
33
Thermostatic Switch (N.C.)
52
H1 Contact Input Selections
All Modes
Closed: Resets faults if the cause is cleared and the Run command is removed.
All Modes
Closed: Decelerates at the Fast Stop time set to C1-09.
All Modes
Open: Motor 1
Closed: Motor 2
All Modes
Open: Decelerates to stop at the Fast Stop time set to C1-09.
All Modes
Triggers the timer set up by parameters b4-01 and b4-02. Must be set in conjunction
with the timer function output (H2-
All Modes
Open: PID control enabled
Closed: PID control disabled
All Modes
(H1-
= 7), and allows the drive to switch between accel/decel times 3 and 4.
All Modes
Open: Parameters cannot be edited (except for U1-01 if the reference source is assigned
to the digital operator).
Closed: Parameters can be edited and saved.
All Modes
Closed: Samples the analog frequency reference and operates the drive at that speed.
All Modes
20: N.O., Always detected, ramp to stop
21: N.C., Always detected, ramp to stop
22: N.O., During run, ramp to stop
23: N.C., During run, ramp to stop
24: N.O., Always detected, coast to stop
25: N.C., Always detected, coast to stop
26: N.O., During run, coast to stop
27: N.C., During run, coast to stop
28: N.O., Always detected, Fast Stop
29: N.C., Always detected, Fast Stop
2A: N.O., During run, Fast Stop
2B: N.C., During run, Fast Stop
2C: N.O., Always detected, alarm only (continue running)
2D: N.C., Always detected, alarm only (continue running)
2E: N.O., During run, alarm only (continue running)
2F: N.C., During run, alarm only (continue running)
All Modes
Closed: Resets the PID control integral value.
All Modes
Open: Performs integral operation.
Closed: Maintains the current PID control integral value.
All Modes
combination of the four terminals set for Multi-Step Speed References 1 to 4.
All Modes
Closed: Closes when thermostatic switches are OFF, and then a TME2 (Transformer
Temperature DI Fault) fault occurs.
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Description
common_
common_
common_
common_
common_
= 12).
common_
common_
common_
common_
common_
common_
common_
common_
common_
Reference
Page
175
175
176
175
176
176
176
176
176
177
178
178
178
178